7.1.5 Preset pressure regulator
Determine setting pressure
An additional pressure regulator is required for connection pressure > 50 mbar.
Set FRS pressure regulator [ch. 7.1.6].
Add the combustion chamber pressure in mbar to the setting pressure.
Determine setting pressure from the table and note down.
The details given for calorific value H
i
relate to 0 °C and 1013 mbar.
The table values have been calculated under ideal conditions. The values are there-
fore guide values for basic settings.
Full load
[kW]
Setting pressure into gas
butterfly valve [mbar]
Min. connection pressure into
isolating valve [mbar]
(low pressure supply)
Nominal diameter valve train
½"
½"
Valve train construction
only W-MF 055
(≤ 50 mbar)
W-MF 055 with
FRS pressure reg-
ulator
(> 50 … 300
mbar)
Natural Gas E: H
i
= 10.35 kWh/m
3
, d = 0.606
25
7.9
12
14
30
7.2
11
14
35
5.9
11
13
40
6.9
12
15
45
8.0
14
17
50
9.3
16
19
Natural Gas LL: H
i
= 8.83 kWh/m
3
, d = 0.641
25
11.4
15
18
30
10.8
15
18
35
8.3
13
16
40
9.6
15
18
45
11.4
18
21
50
13.3
20
23
Liquid Petroleum Gas: H
i
= 25.89 kWh/m
3
, d = 1.555
The selection is calculated for Propane, it can however, also be used
for Butane.
25
8.4
11
14
30
5.9
9
12
35
6.4
10
12
40
6.5
10
13
45
7.4
12
14
50
8.4
13
15