Installation and operating instruction
Gas burner WG10…/0-D ZM-LN
6 Operation
83300902 1/2019-02 La
33-112
6.2.1 Info level
Burner data can be interrogated in the Info level .
Press [Enter] for approx. 0.5 seconds.
The Info level is activated.
Press [Enter] to reach the next information.
l,m³
No.
Information
0
Total gas consumption in m
3
(via X3:8)
Reset value:
Press [L/A] and [+] simultaneously for approx. 2 seconds.
1
Hours run
2
– no function –
3
Burner starts
4
Device item number
5
Index of device item number
6
Device number
7
Production date (DDMMYY)
8
Fieldbus address
9
Valve proving behaviour
11
Not used
12
Current gas consumption (0.1 m
3
/h)
13
Analogue module EM3/3 or Fieldbus module EM3/2 available
0
: no
1
: yes
After information
13
or a waiting time of approx. 20 seconds the combustion man-
ager changes over to the operating level.