Installation and operating instruction
Combustion manager W-FM 100 und W-FM 200
6 Operation
83054802 1/2018-07 La
75-228
Local / Remote
Setting
Function
local
The operating modes for the load controller via Bus
ExtLC Bus
or
IntLC Bus
have no influence
[ch. 6.12.2].
The internal load controller takes over the control and the
internal setpoint W1 is activated.
remote
Setting for load control via Bus [ch. 6.12.2].
If the operating mode
ExtLC Bus
has been selected,
the building management system determines the load.
If operating mode
IntLC Bus
has been selected, the
building management system determines the setpoint.
If Modbus communication fails, the W-FM automatically
changes into
local
mode. When communication is
restored, the mode has to be set to
remote
either via
the ABE or via Modbus signal.
Remote mode
Parameter
Remote mode
is read only, the setting is made via Modbus (building
management system).
Setting
Function
Auto
Setpoint W3 is determined by the building management
system.
On
Load is determined by the building management system.
Off
The internal load controller takes over the control.
External setpoint W3
Parameter
W3
is read only, the setting is made via Modbus (building management
system).
6.6.4 Trending data
Operation
OptgModeSelect
Type of Gateway
Data output
In Bus protocol
Data output
the interface COM 2 sends trending data for data
recording.
Interface configuration in menu
Modbus
is required for data output [ch. 6.6.3].
Data recording is not possible for diagnostic purposes during servicing and without
peripherals and software.