Installation and operating instruction
Combustion manager W-FM 100 und W-FM 200
9 Troubleshooting
83054802 1/2018-07 La
199-228
9.3 Lockout
If a lockout condition occurs, the combustion manager initiates a fault shutdown
and burner lockout.
The display and operating unit alternately shows the shutdown behaviour and the
fault diagnosed as a plain text display.
Once the fault has been rectified, the combustion manager has to be reset for re-
start.
Example
Lockout
Air pressure is
off
Lockout history
OperationalStat
LockoutHistory
Parameter
LockoutHistory
alternately displays the last 9 faults as plain text or
diagnostic display [ch. 9.4].
Select History using dial knob and confirm with [Enter].
Browse history with the dial knob.
The display changes every 5 seconds between plain text and diagnostic display.
The [Enter] key can be used to manually change the display.
Exit History using [esc] key.
Normal operation
Status/Reset
Fault history
Lockout history
Air pressure is
off
1 01.04.15 13:22
C:28 D:00 P:62
Start No. 22
Load:79.6 Gas
9 06.11.15 08:15
C:31 D:00 P:81
Start No. 4711
Load:25.0 Gas
5 sec
The diagnostic display provides information about:
Fault number (
1
…
21
)
Date when fault occurred (
dd.mm.yy
)
Time when fault occurred (
hh.mm
)
Fault code (
C:
)
Diagnostic code (
D:
)
Operating phase when fault occurred (
P:
)
Number of burner starts (
Start No.
)
Load setting or stage when fault occurred (
Load:
)
Current fuel when fault occurred (
Oil
or
Gas
)