background image

 

 
 
 
 
 
 
 

Installation and Startup Guide

 

This document covers the installation of MT8050iE Series HMI, for the detailed specifications and 
operation, please refer to Brochure and EasyBuilder Pro User Manual. 

Install Environment: 

NEMA Rating

 

MT8050iE

 Series HMI is NEMA 4 rated (Indoor Only). 

 

Electrical 
Environment

 

The 

MT8050iE

 Series has been tested to conform to European CE requirements. 

This means that the circuitry is designed to resist the effects of electrical noise. 
This does not guarantee noise immunity in severe cases. Proper wire routing and 
grounding will insure proper operation.

 

Environmental 
Considerations

 

(1)  Make sure that the displays are installed correctly and that the operating 

limits are followed. Avoid installing units in environments where severe 
mechanical vibration or shocks are present. 

(2) 

Do not operate the unit in areas subject to explosion hazards due to 
flammable gases, vapors or dusts.

 

(3)  Do not install the unit where acid gas, such as SO2 exists. 

(4) 

This device should be mounted in the vertical position and for use on the flat 
surface enclosure.

 

(5) 

Conform to UL508 (ISBN 0-7629-0404-6) machine safety for use in 
Pollution Degree 2 Environment.

 

 

Unpacking the Unit

 

Unpack and check the delivery. If damage is found,   
notify the supplier.   

Installation Instructions 

Secure the operator panel in position, using all the fastening holes and the provided brackets   
and screws: 
 

 

 

Type 

A(mm) 

B(mm) 

MT8050iE 

119 

93 

 

 

Power Connections 

 

System Settings 

When HMI powered up and displays image,   
click the system setting button. 
(Default System Password: 111111) 

It is necessary

 to connect the HMI to   

your network through a RJ-45 cable.   
 
 
 
 
 
 
 
 
 
 
 
 
 

 

MT8050iE series 

   

Installation Instruction 

NOTE:   

Place the operator panel on a stable 
surface during installation. Dropping it or 
letting it fall may cause damage. 

g

g

p

( Note 1: For the details of HMI 
DIP SW function settings please 
refer to Part 8 in this guide. )

 

Go to the Network tab, you may choose 
to auto get DHCP IP, or designate your 
own IP.

 

NOTE:   

1. 

Conne

ct positive DC line to the ‘+’ termin

al 

and the DC 

ground to the ‘

-

 terminal. 

 

2. Please do not connect HMI with PLC and PC 
simultaneously to prevent potential difference 
from destroying USB ports of HMI and PC. 
 
To make a connection, strip abou

t 3/8” of 

insulation off the end of the wire, turn the 
connector screw counterclockwise until the gap 
is wide open, insert the wire all the way in, and 

turn the screw clockwise until it’s tight.

 

(A) 

(B) 

Cutout 

(1) Installation Instruction, 2-sided A4 *1 

(2) Human Machine Interface *1

 

(3) Power Connector *1

 

(4) Brackets & Screws V3.0 *1 pack

 

3

otify the supplier.

(1) 

 

(2) 

 

 

 
 

(4) 

(3) 

Reviews: