Installation and Startup Guide

 

This document covers the installation of 

MT6/8071iP

 Series HMI, for the detailed specifications and 

operation, please refer to Brochure and EasyBuilder Pro User Manual. 

Install Environment: 

NEMA Rating

 

MT6/8071iP Series HMI is NEMA 4 rated (Indoor Only). 

 

Electrical 
Environment

 

MT6/8071iP Series has been tested to conform to European CE requirements. 
This means that the circuitry is designed to resist the effects of electrical noise. 
This does not guarantee noise immunity in severe cases. Proper wire routing and 
grounding will insure proper operation.

 

Environmental 
Considerations

 

(1)  Make sure that the displays are installed correctly and that the operating 

limits are followed. Avoid installing units in environments where severe 
mechanical vibration or shocks are present. 

(2) 

Do not operate the unit in areas subject to explosion hazards due to 
flammable gases, vapors or dusts.

 

(3)  Do not install the unit where acid gas, such as SO2 exists. 

(4) 

This device should be mounted in the vertical position and for use on the flat 
surface enclosure.

 

(5) 

Conform to UL508 (ISBN 0-7629-0404-6) machine safety for use in 
Pollution Degree 2 Environment.

 

(6) 

Relative Humidity: 10% ~ 90% (non-condensing)

 

 

Unpacking the Unit

 

Unpack and check the delivery. If damage is found, notify the supplier.   

NOTE: 

Place the operator panel on a stable surface during installation. Dropping it or letting it fall 

may cause damage.

 

(1)  Installation Instruction, 2-sided A4 *1 
(2)  Human Machine Interface *1 
(3)  Power Connector *1 
(4)  Brackets & Screws *1 pack 
 

Installation Instructions 

Secure the operator panel in position, using 
all the fastening holes and the provided 
brackets and screws. Screw Torque: 2.6 ~ 
3.9 lbf.in. (For reaching waterproof effect 
and preventing the panel from being 
deformed.) Panel Cutout: 192 mm x 138 mm 
 

 

 

 

Power Connections 

NOTE:   
1. Connect positive DC line to the ‘+’ terminal and the 
DC ground to the ‘-’ terminal. 

 

2. When downloading project using a USB cable, do 

not connect HMI with PLC and PC simultaneously, for 

electric potential difference may result in damage to 

HMI or PC. 

 

 

System Settings 

When HMI is powered up and displays image,   
click the system setting button. 
(Default System Password: 111111)

 

 

It is necessary

 to connect the HMI to   

your network through a RJ-45 cable. 
(N/A for MT6071iP) 
 
 
 
 
 
 
 
 

 

 

 

EasyBuilder Pro Software Settings 

Launch EasyBuilder Pro software, select your project file, press F7 shortcut key to open the download 
dialog box:   

 
For MT6071iP, select USB cable /   
For MT8071iP, select Ethernet > IP tab > Enter your HMI IP > Click Download to download this project file 
to HMI. 
 
Using screensaver and backlight saver is recommended in order to avoid image persistence caused by 
displaying the same image on HMI for a long time. 
 
( Please refer to EasyBuilder Pro User Manual for software operation details ) 
 
 
 
 
 
 

MT6071iP MT8071iP series 

                                                                                                                   

Installation Instruction 

Go to the Network tab, you may choose 
to auto get DHCP IP, or designate your 
own IP.

 

 