background image

1

 

MT-600 series 

 

MT-615X 

 

Installation Instruction 

 

1.0 Installation and Startup Guide   

Install Environment 

 

Where  
Used

 

The MT-600 Series is designed for industrial. The temperature range of operating is 
from 32 to 113 °F (0 to 45 °C) , as majority of industrial environments. It may not be 
suitable for using in certain outdoor applications. Please consult the factory for 
advised usage in outdoor applications. 

NEMA 
Rating 
 

The MT-600 Series front bezel is NEMA 4 rated. When installed properly in a NEMA 
4 panel, the NEMA 4 rating of the panel will not be compromised. This means that 
fluids will not enter the panel during wash downs. 

Electrical 
Environment 

The MT-600 Series has been tested to conform to European CE requirements. This 
means that the circuitry is designed to resist the effects of electrical noise. This does 
not guarantee noise immunity in severe cases.    Proper wire routing and grounding 
will insure proper operation. 

Mechanical 
Environment 

 
 
 
 

Avoid installing units in environments where severe mechanical vibration or shocks 
are present. 

2.0 Installation Instructions 

2.1 Mounting Instructions 

 

2.1.1 Location Considerations 

 

Care should be taken when locating equipment behind the unit to ensure that AC power wiring, PLC 

output modules, contactors, starters and relays, and any other source of electrical interference are located 
away from the back of the unit. 

 
Particular note should be taken to the position of variable speed drives and switching power supplies. 

Their input and load cables should be screened to a central star earth point. 

 

Summary of Contents for MT-615X

Page 1: ...en tested to conform to European CE requirements This means that the circuitry is designed to resist the effects of electrical noise This does not guarantee noise immunity in severe cases Proper wire...

Page 2: ...mmable gases vapors or dusts z The unit should not be installed where fast temperature variations and or high humidity are present This will cause condensation of water in the device z Do not install...

Page 3: ...ower supply return point to the central star earth point Ground conductors should be as short and as large in size as possible The conductors must always be large enough to carry the maximum short cir...

Page 4: ...intended as safeguards against the failure of critical components and the effects of such failures or the inadvertent errors that might be introduced if programs are changed while the equipment is in...

Page 5: ...5 COM3 RS 485 COM3 RS 232 Pin assignment of the 9 Pin Female SUB D COM1 RS 485 COM3 RS 485 and COM3 RS 232 Port Pin Symbol Com1 RS485 2w Com1 RS485 4w Com3 RS485 Com3 RS232 1 Rx Data Rx 2 Rx Data Rx 3...

Page 6: ...chinery Directive 89 392 EEC 91 368 EEC 93 44 EEC 93 68 EEC machine safety z MT600 products will be CE marked to indicate compliance with the EMC Directive The MT 600 Series has been designed to opera...

Page 7: ...core processor Flash memory N A DRAM 256MB on board DDR 400MHz SDRAM CompactFlash card slot Type II x 1 RTC Built in General Specification Input Power 24 5 VDC Power Consumption 1A 24VDC CE Complies w...

Page 8: ...5 2 4W COM3 RS232 USB HOST MINI USB PS 2 E G H I J K L M F Rear View Bottom View Side View Panel mounting clamp slots 10 places Cutout dimensions MT 615 352mm 13 86 W x 279mm 10 98 H D sub VGA out N A...

Reviews: