Weil-McLain 94 Specification Sheet Download Page 1

 

 
I. General 

Requirements 

 

A.  Furnish and install (    ) low pressure, wet base, cast iron sectional boiler(s) with power 

burner(s) that pressurize the firebox and operate under forced and balanced draft. 

 

B.  Assemble and install boiler-burner unit(s) in compliance with manufacturers installation 

instructions. All work must be done in a neat and workman like manner. 

 

C.  Weil-McLain (P)(A)(B) L, (P)(A)(B) G, (P)(A)(B) GL- (   )94-(W) (S)F boiler(s) with 

burner(s) capable of burning natural gas at (  )” W.C. inlet pressure and/or No. 2 fuel oil. 

1.  (B) Boiler-burner unit Field assembled (standard). 
2.  (A) Boiler-burner unit with factory assembled sections (to size 21 only). 
3.  (P) Boiler-burner unit completely packaged and fire tested (to size 21 only). 
4.  Natural gas fired and/or No. 2 fuel oil. 
5.  Water or steam. 
6.  Forced or balanced draft. 
 

D.  Boiler(s) shall have I=B=R Hydronics Institute gross output(s) at 100% firing rate –  
      (    ) MBH per boiler. 

 

E.  Boiler(s) shall be manufactured by ISO 9001 registered company to conform to Section 

IV of the ASME Boiler and Pressure Vessel Code. 

1.  Individual sections (and section assembly) to be hydrostatically pressure tested at 

factory in accordance with ASME requirements. 

2.  Maximum allowable working pressure 50 PSIG water and 15 PSIG steam cast as 

part of section with ASME symbol (Water only: optional 80 PSIG stamped in 
section in place of 50 PSIG). 

 

F. Regulatory Requirements 

1.  Boiler(s) and controls to comply with applicable regulations. 
2.  Provide UL labeled burner(s). 
3.  Provide add option for local code(s) ie: MASS Code BAR 

 

G. Submittals 

1.  Submit shop drawings and product data. 

2.

 

Submittal packet to include boiler (and burner) manufacturer descriptive literature, 
installation instructions, operating instructions, and maintenance instructions.

 

 
 

II. Product 

 

A. Acceptable 

boiler/burner 

manufacturer(s) include(s): 

1. Weil-McLain only, as specified in Part 1, Paragraph C.  

94 SERIES BOILER

 

SUGGESTED SPECIFICATIONS 

Summary of Contents for 94

Page 1: ...output s at 100 firing rate MBH per boiler E Boiler s shall be manufactured by ISO 9001 registered company to conform to Section IV of the ASME Boiler and Pressure Vessel Code 1 Individual sections and section assembly to be hydrostatically pressure tested at factory in accordance with ASME requirements 2 Maximum allowable working pressure 50 PSIG water and 15 PSIG steam cast as part of section wi...

Page 2: ... Boiler s Provided with cast in air elimination to separate air from circulating water Provided with expansion tank tapping to divert separated air to expansion tank Constructed to provide balanced water flow through entire section assembly using single supply and return connections for water No external headers are necessary for water Steam requires an external header 24 minimum from the waterlin...

Page 3: ... temperature gauge with dial clearly marked and easy to read 4 ASME certified pressure relief valve set to relieve at 30 PSIG Optional relief valves available up to and including maximum allowable pressure Side outlet discharge type contractor to pipe outlet to floor drain or near floor avoiding any area where freezing could occur b Steam boiler s standard controls furnished 1 Low pressuretrol ope...

Page 4: ...er to be adjusted to provide 9 5 to 10 0 CO2 for gas and or 11 5 to 12 CO2 with zero smoke for oil firing 9 Burner s manufactured by Power Flame Gordon Piatt 10 Burner operating mode on off low high off low high low modulating A Panel options power on fuel on light is standard on all burner s with panels 1 Call For Heat 2 Ignition On 3 Pilot Failure 4 Low Water 5 Flame Failure 6 Silencing Switch 7...