Connecting the SAI Distributor
5.9
SAI-AU M12 SB 8DO 2A
The SAI distributor Active Universal is equipped with
the functions of a decentralised I/O system. Each
distributor is equipped with module-specific actua-
tor/sensor functions and a Fieldbus interface. The
modules combine the complete electronics in a wa-
ter- and dust-proof protected housing. That enables
their use in harsh environments.
The module SAI-AU M12 SB 8DO 2A is designed to
connect 8 digital actuators. The outputs are de-
signed for a load current of 2.0 A.
The signals are connected via four M12 plug-in con-
nectors.
Figure 40
SAI-AU M12 SB 8DO 2A
HINWEIS
After a change of the Subbus modules is
in many situations a new start of the ga-
teway necessary.
LEDs
UB
Supply voltage UB
Supply for the module and
the plug-in stations 1 though
4.
UQ1
Supply voltage UQ1
Supply for the outputs
O1...O4
UQ2
Supply voltage UQ2
Supply for the outputs
O5...O8
Com
Communication with the
gateway
DO1 to DO8
Digital outputs
Connections
AUX IN
Supply voltage UQ1, UQ2
SUB IN
Sub-bus input
SUB OUT
Sub-bus output
1 to 4
8 outputs
Table 45
SAI-AU M12 SB 8DO 2A
5663600000/1.4/09.09
67
Summary of Contents for SAI Active Universal Pro Series
Page 2: ......
Page 10: ...Notes on Safety 10 5663600000 1 4 09 09...
Page 11: ...SAI Pro 2 SAI Pro 2 1 Pro Description 12 2 2 PROFIBUS DP 14 5663600000 1 4 09 09 11...
Page 20: ...Project Planning with the Universal Pro 20 5663600000 1 4 09 09...
Page 28: ...Mounting SAIs 28 5663600000 1 4 09 09...
Page 95: ...Connecting the SAI Distributor 5663600000 1 4 09 09 95...
Page 177: ......