Operation and Maintenance Manual and User Service Guide for Industrial Power WP10 Series Diesel Engine
34
negative pole of power supply is grounded, the negative pole of battery
should be grounded at the negative pole of battery rather than at the
negative pole (1 pin) of controller.
c.
If the power supply wire has length of less than 10m, its diameter
should be more than 0.75 mm
2
(include) and if the power supply wire
has length of more than 10mm, thicken it.
5.12.6 Daily maintenance of electronic governor
a.
Timely replace or repair any damaged cable. Cable should be clamped
to prevent against rubbing with engine. In addition, the layout of cable
should be kept away from the high-temperature parts (such as
supercharger and exhaust pipe).
b.
Check whether the executor is reliably installed.
c.
Check whether the executor connector, sensor connector and cable
screws are contaminated with oil or loosened, if so, timely clean or
tighten them.
d.
Check whether the battery electricity is sufficient, or whether the
charger is normal.
e.
For the non-forced circulation oil pump, frequently check the high/low
oil level, and replace the lubricant on schedule.
f.
If the engine is started at low temperature, push the rocker arm of
Battery
Generator for
charging
Starter motor
Relay
Speed
controller