Troubleshooting and Maintenance
5
5-2 | UR11
Table 5.1 -
Operation of faults and alarms
Name
Description
Inputs.
+24 Vdc.
+24 Vdc power supply of the CIR11 board.
R, S, T.
R1, S1, T1, R2, S2 and T2 input power connections.
Pre-charge.
Pre-charge status: "Not-performed", "In progress" or "Completed".
Temperature.
UR11 heatsink temperature measured through the NTCs.
RL outputs. RL1.
Relay output with the pre-charge status indication function (UDC1_OK & UDC2_OK). It closes when the two
UR11 rectifier diode bridges completed the pre-charge.
RL2.
Output relay with "No Temperature Alarm" function. It opens under alarm condition.
RL3.
Output relay with "No Temperature Fault" function. It opens under fault condition.
LEDs.
12 V ON.
Green LED with +12 V ON power supply indication, generated at CIR11 from the + 24 Vdc.
UDC_1 OK.
Green LED with status function indication of one UR11 input rectifier bridge - it lights when its pre-charge is
completed.
UDC_2 OK.
Green LED with status function indication of the other UR11 input rectifier bridge - it lights when its pre-charge
is completed.
TEMP_ALARM.
Yellow LED that lights when the UR11 temperature is too high (alarm).
TEMP_FAULT.
Red LED that lights under overtemperature or undertemperature fault condition
Table 5.2 -
Faults, alarms and possible causes
Inputs
Outputs
LEDs
Possible Causes
+24 Vdc
R, S, T
Pre-charge Temperature RL1 RL2 RL3
+12 V
ON
UDC_1
OK
UDC_2
OK
Temp
Alarm
Temp
Fault
OK
OFF
OFF
T
MIN
≤ T ≤ T
AL
OFF ON ON ON
OFF
OFF
OFF OFF
+ 24 Vdc applied to the control
circuit (CIR11) and the main power
supply (R, S and T) is missing. Ready
for power energization.
OK
OK
In progress
(1)
T
MIN
≤ T ≤ T
AL
OFF ON ON ON
OFF
OFF
OFF OFF
Power supply connected, pre-charge
in progress.
OK
OK
Completed T
MIN
≤ T ≤ T
AL
ON ON ON ON
ON
ON
OFF OFF REGULAR OPERATION.
OK
Phase fault
undervoltage.
OFF
T
MIN
≤ T ≤ T
AL
OFF ON ON ON
OFF
(2)
OFF
(3)
OFF OFF
Phase fault or undervoltage at the
input power
(2)
(3)
.
Open fuse.
Open circuit breaker.
OK
OK
OFF
T
MIN
≤ T ≤ T
AL
OFF ON ON ON
OFF
(2)
OFF
(3)
OFF OFF
Defective UR11.
OK
OK
Completed
T
AL
(4)
< T
ON OFF ON ON
ON
ON
ON
OFF
Heatsink temperature higher
than 80 °C (176 °F) (alarm
temperature).
OK
OK
OFF
T
FAULT
(4)
< T OFF OFF OFF ON
OFF
OFF
ON
ON
Heatsink overtemperature,
higher than 90 °C (194 °F) (fault
temperature).
OFF
(5)
(5)
(5)
OFF OFF OFF OFF
OFF
OFF
OFF OFF
Control (CIR11) w24 Vdc
power supply.
OK
OK
OFF
T < T
MIN
OFF ON OFF ON
OFF
OFF
OFF
ON
Heatsink undertemperature, smaller
than -9 °C (16 °F).
Defective or opened NTC.
Note:
(1)
Temporary operation condition.
(2)
Phase fault / undervoltage / defective rectifier bridge 1 - refer to
(3)
Phase fault / undervoltage / defective rectifier bridge 2 - refer to
(4)
The monitoring temperatures are:
-
High temperature alarm: active with T
AL
≅
80 ºC (TEMP_ALARM).
-
Overtemperature fault: active with T
FAULT
≅
90 ºC (TEMP_FAULT).
-
Undertemperature fault: active with T
MIN
≅
-9 ºC (TEMP_FAULT).
(5)
The input state is not decisive for the outputs state.