Parameter
Description
Range of values
Decimal
places
Instance
Class=A2h Attr=5
CIP data type
Net Id
Size
Qty mapped
words
12 = Communication
13 = I motor % > Value
14 = Breaker Shunt Trip
C4.2.4
DO Comparison Value
10.0 to 500.0 %
1
278
UINT
278
16bit
1
C4.3
Analog Output
C4.3.1
Function
251
USINT
251
enum
1
0 = Not Used
1 = SSW Current %
2 = Line Voltage %
3 = Output Voltage %
4 = Power Factor
5 = Thermal Class Prot.
6 = Output Power W
7 = Output Power VA
8 = Motor Torque %
9 = Value to AO
10 = SCRs Temperature
11 = SoftPLC
C4.3.2
Gain
0.0 to 9.999
3
252
UINT
252
16bit
1
C4.3.3
Signal
253
USINT
253
enum
1
0 = 0 to 20mA
1 = 4 to 20mA
2 = 20mA to 0
3 = 20 to 4mA
4 = 0 to 10V
5 = 10V to 0
C5 Configurations\Protections
C5.1
Voltage Protections
C5.1.1
Motor Undervoltage
C5.1.1.1
Mode
900
USINT
900
enum
1
0 = Inactive
1 = Fault F002
2 = Alarm A002
C5.1.1.2
Level
0 to 30 %Vn
0
901
USINT
901
8bit
1
C5.1.1.3
Time
0.1 to 10.0 s
1
902
USINT
902
8bit
1
C5.1.2
Motor Overvoltage
C5.1.2.1
Mode
903
USINT
903
enum
1
0 = Inactive
1 = Fault F016
2 = Alarm A016
C5.1.2.2
Level
0 to 20 %Vn
0
904
USINT
904
8bit
1
C5.1.2.3
Time
0.1 to 10.0 s
1
905
USINT
905
8bit
1
C5.1.3
Motor Voltage Imbalance
C5.1.3.1
Mode
906
USINT
906
enum
1
0 = Inactive
1 = Fault F001
2 = Alarm A001
C5.1.3.2
Level
0 to 30 %Vn
0
907
USINT
907
8bit
1
C5.1.3.3
Time
0.1 to 10.0 s
1
908
USINT
908
8bit
1
SSW900
|
49