C CONFIGURATIONS
C8.1.2 Data Write
C8.1.2.25 Word #20
Range:
0 ... 65535
Default:
0
Properties:
Stopped
Description:
Select the net address of other parameter, which content will be available as writing data for fieldbus interfaces
(outputs: received from master).
The data size of the referenced parameter must be considered. If data size is bigger than 16 bits, the next data write
word configuration must be set to the same net address.
C8.3 Anybus-CC
Configuration for the Anybus-CC communication and protocols that use this interface.
For a detailed description, refer to the SSW900 Anybus-CC User’s Manual specific for the desired protocol, supplied
in electronic format.
C8.3 Anybus-CC
C8.3.1 Update Configuration
Range:
0 ... 1
Default:
0
Properties:
Stopped
Description:
It allows forcing a reinitialization of the Anybus-CC communication module for the configurations done in the
parameters of menus C8.1 and C8.3 to be applied.
The reinitialization implies communication loss. After the process is completed, this parameter automatically goes
back to Regular Operation.
Indication
Description
0 = Normal Operation
No action.
1 = Update configuration
Reinitializes the Anybus module.
C8.3 Anybus-CC
C8.3.4 IP Address Configuration
Range:
0 ... 2
Default:
1
Properties:
Description:
It allows to choose how to set the IP address for the modules Anybus-CC EtherNet/IP, Modbus TCP and PROFINET
IO.
Indication
Description
0 = Parameters
The programming of the IP address, configurations of the subnet mask and gateway
must be done through parameters C8.3.5, C8.3.6 and C8.3.7.
1 = DHCP
Enables the DHCP function. The IP address and other network configurations are
received from a DHCP server via network.
2 = DCP
The IP address and other network configurations are received via DCP (PROFINET IO).
✓
NOTE!
After changing this configuration, for the modification to be effective, the equipment must be turned off
and then turned on again, or the configurations must be updated through C8.3.1.