Parameterization
5-10 | SRW 01
5
5.4 OPERATION MODES
The SRW 01 presents 8 operation modes. The operation mode is selected through the parameter P202.
P202 – Operation Mode
Adjustable
Range:
0 = Transparent
1 = Overload Relay
2 = Direct Starter
3 = Reversing Starter
4 = Star/Delta Starter
5 = Dahlander Starter
6 = Pole Changing Starter
7 = PLC
Factory
Setting:
1
Proprieties:
Sys, CFG
Description:
It is the selection of the SRW 01 operation mode.
The functions of the Control Unit inputs and outputs are configured automatically according to the selected
operation mode, defining in a fast and simple manner the wiring between pushbuttons, contactors and the
SRW 01, for the assembling of a motor starter. The Control Unit digital inputs and outputs can be monitored via
Ladder/Fieldbus, even though they have specific pre-defined functions.
All the operation modes, except PLC, allow the motor monitoring.
ATTENTION!
It is only possible to change the parameter P202 with the motor deenergized.
NOTE!
The operation mode change (P202) modifies the functions of the Control Unit digital inputs and outputs.
NOTE!
The command functions (ON/OFF), preset for the digital inputs in each operating mode, except for
Overload, PLC and Transparent mode, can be modified by means of the system bit markers, SX3001
(OFF), SX3002 (Direct ON/High Speed) and SX3003 (Reverse ON/Low Speed). Use those markers on
the Ladder user’s program and configure the local command selection (P229) or remote command
(P232) for value 2 (USB/Ladder).
NOTE!
All operation modes allows the user to develop its own application using the WLP software ladder
language. The maximum allowed program size is 32 kB.
5.4.1 SRW 01 Check Back
Parameters P208, P209 and P211 configure the check back of the SRW 01 for each operation mode which
assures that the motor was really driven and checking if it keeps this way until a stop control is identified or
assuring that the motor keeps at standstill until a start control is identified. The digital inputs that can be used as
check back depend on the operation mode (P202). Consult the following connection schemes.