S STATUS
4 S STATUS
Allows accessing starter manager SCW100 reading variables.
S4 COMMUNICATION
Read parameters that display information about the communication interfaces for the product.
S4 Communication
P0030: CAN - Address
Range:
1 ... 127
Default:
1
Description:
It allows viewing the address configured for CAN communication, programmed using DIP switches S1 and S2.
S4 Communication
P0031: CAN - Baudrate
Range:
0 ... 7
Default:
0
Description:
It allows viewing the value of the baud rate for the CAN interface, programmed using DIP switch S3, in bits per
second.
Indication
Description
0 = 1 Mbit/s
CAN baud rate.
1 = 800 Kbit/s
CAN baud rate.
2 = 500 Kbit/s
CAN baud rate.
3 = 250 Kbit/s
CAN baud rate.
4 = 125 Kbit/s
CAN baud rate.
5 = 100 Kbit/s
CAN baud rate.
6 = 50 Kbit/s
CAN baud rate.
7 = 20 Kbit/s
CAN baud rate.
S4 Communication
P0033: CAN - Controller Status
Range:
0 ... 5
Default:
0
Description:
It allows identifying if the CAN interface is enabled and if the communication presents errors.
Indication
Description
0 = Disabled
Inactive CAN interface.
1 = Reserved
-
2 = CAN Enabled
CAN interface is active and without errors.
3 = Warning
CAN controller has reached the warning state.
4 = Error Passive
CAN controller has reached the error passive state.
5 = Bus Off
CAN controller has reached the bus off state.
S4 Communication
P0034: CAN - RX CAN Telegrams
Range:
0 ... 65535
Default:
0
Description:
This parameter works as a cyclic counter that is incremented every time a CAN telegram is received. It informs the
operator if the device is being able to communicate with the network.
SCW100 | 13