5
DETAILED PARAMETER DESCRIPTION
✓
NOTE!
This parameter is only visible on the HMI when: P0950 = 1 (Synchronous motor with brushes).
This parameter is only visible on the HMI when: the control type is vector, P0202 = 3 (Sensorless
Vector) or P0202 = 4 (Vector with Encoder).
P0439 - Integration constant of the current regulator IQ
Adjustable range:
0.1 to 999.9
Factory setting:
9.0
Acesso:
Menu
→
Configurations
→
Control
Description:
Parameter used by the regulator to control the currents.
✓
NOTE!
This parameter is only visible on the HMI when: P0950 = 1 (Synchronous motor with brushes).
This parameter is only visible on the HMI when: the control type is vector, P0202 = 3 (Sensorless
Vector) or P0202 = 4 (Vector with Encoder).
P0440 - Proportional gain of the current regulator ID
Adjustable range:
0.000 to 9.999
Factory setting:
0.074
Acesso:
Menu
→
Configurations
→
Control
Description:
Parameter used by the regulator to control the currents.
✓
NOTE!
This parameter is only visible on the HMI when: P0950 = 1 (Synchronous motor with brushes).
This parameter is only visible on the HMI when: the control type is vector, P0202 = 3 (Sensorless
Vector) or P0202 = 4 (Vector with Encoder).
P0441 - Integration constant of the current regulator ID
Adjustable range:
0.1 to 999.9
Factory setting:
19.6
Acesso:
Menu
→
Configurations
→
Control
Description:
Parameter used by the regulator to control the currents.
✓
NOTE!
This parameter is only visible on the HMI when: P0950 = 1 (Synchronous motor with brushes).
This parameter is only visible on the HMI when: the control type is vector, P0202 = 3 (Sensorless
Vector) or P0202 = 4 (Vector with Encoder).
MVW3000 | 5-78
Summary of Contents for MVW3000 Series
Page 2: ......
Page 58: ...1 QUICK REFERENCE OF PARAMETERS AND FAULTS MVW3000 1 52...
Page 62: ...2 SAFETY INSTRUCTIONS MVW3000 2 4...
Page 192: ...6 SPECIAL FUNCTIONS MVW3000 6 4...
Page 262: ...7 DIAGNOSTICS AND TROUBLESHOOTING MVW3000 7 70...
Page 263: ......