CONNECTING A DEVICE TO THE DRIVE SCAN
5.7.3.1 Attributes Cyclically Monitored by the SRW01
Parameter
Description
Atributo
Acquisition type
Class
P002
Current (%)
ratedCurrent
Last value
measurement
P003
True RMS current
motorCurrent
Valor médio
measurement
P004
True RMS line voltage
lineVoltage
Last value
measurement
P006
Relay status
status
Last value
measurement
P008
Power factor
powerFactor
Valor médio
measurement
P009
Motor reactive power
reactivePower
Last value
measurement
P010
Motor active power
outputPower
Valor médio
measurement
P011
Motor apparent power
apparentPower
Last value
measurement
P014
Last fault
lastFault
Last value
diagnostic
P016
Current error
currentError
Last value
diagnostic
P020
PTC value (ohms)
ptcValue
Last value
measurement
P030
R phase true RMS current
phaseCurrentR
Last value
measurement
P031
S phase true RMS current
phaseCurrentS
Last value
measurement
P032
T phase true RMS current
phaseCurrentT
Last value
measurement
P033
L1-L2 line voltage
lineVoltageRs
Last value
measurement
P034
L2-L3 line voltage
lineVoltageSt
Last value
measurement
P035
L3-L1 line voltage
lineVoltageTr
Last value
measurement
P036
Earth leakage current (%)
earthLeakage
Last value
measurement
P037
True RMS earth leakage current
eathLeakageCurrent
Last value
measurement
P042
Energized hours
energizedHours
Last value
diagnostic
P043
Motor on hours
motorOnHours
Last value
diagnostic
P044
kWh counter
energyCounter
Last value
measurement
P050
Thermal protection
thermalProtection
Last value
measurement
P051
Current imblance level
currentUnbalance
Last value
measurement
P052
Earth fault imbalance
earthFault
Last value
measurement
P053
Voltage imbalance level
voltageUnbalance
Last value
measurement
P060
Total starts number
startsNumber
Last value
measurement
P061
Overload trips
overloadTrips
Last value
measurement
P062
Current imbalance trips
currentUnbalanceTrips
Last value
measurement
P063
Earth fault trips
earthFaultTrips
Last value
measurement
P064
Phase fault trips (current)
currentPhaseFaultTrips
Last value
measurement
P065
Overcurrent trips
overcurrentTrips
Last value
measurement
P066
Undercurrent trips
undercurrentTrips
Last value
measurement
P067
Phase out of range trips
outOfPhaseTrips
Last value
measurement
P068
PTC trips
ptcTrips
Last value
measurement
P069
Earth leakage trips
earthLeakageTrips
Last value
measurement
P070
External fault trips
externalFaultTrips
Last value
measurement
P071 a P073
Trip 1 to 3 status
tripStatus1 a tripStatus3
Last value
status
P075 a P077
Alarm 1 to 3 status
alarmStatus1
Last value
status
P082
Total trips
totalTrips
Last value
measurement
P100
Voltage imbalance trips
voltageUnbalanceTrips
Last value
measurement
P101
Out of phase trips
outOfPhaseTrips
Last value
measurement
P102
Overvoltage trips
overvoltageTrips
Last value
measurement
P103
Undervoltage trips
undervoltageTrips
Last value
measurement
P104
Underpower trips
underpowerTrips
Last value
measurement
P105
Overpower trips
overpowerTrips
Last value
measurement
P106
Power underfactor trips
powerUnderfactorTrips
Last value
measurement
P107
Power overfactor trips
powerOverfactorTrips
Last value
measurement
P110 a P111
Trip 4 to 5 status
tripStatus4 a tripStatus5
Last value
status
P115 a P116
Alarm 4 to 5 status
alarmStatus1 a alarmStatus5
Last value
status
Low Voltage Devices | 5-26