HVAC Functions
18-26 | CFW501
18
P1076 – Value for Low Level Alarm of the Process Variable of the External PID
Controller
Adjustable
Range:
-32768 to 32767
Factory
Setting:
2
Properties:
Access groups
via HMI:
HVAC
Description:
This parameter defines the value below which it will be considered low level for the process variable of the
external PID controller according to its engineering unit.
NOTE!
This parameter will be viewed according to the selection of the parameters for the engineering unit
2 (P0512 and P0513).
P1077 – Time for Low Level Alarm of the Process Variable of the External PID
Controller
Adjustable
Range:
0.00 to 650.00 s
Factory
Setting:
5.00 s
Properties:
Access groups
via HMI:
HVAC
Description:
This parameter defines the time with the low level condition of the process variable of the external PID controller,
so that the alarm message “A0786: Low level alarm of the process variable of the external PID controller” will
be generated. With P1075 programmed for 2, the fault “F0787: Low level fault of the process variable of the
external controller” will be generated after the motor driven by the CFW501 frequency inverter is decelerated
and is no longer spinning.
NOTE!
The value set to 0.00 s disables the alarm detection.
Summary of Contents for CFW501 V1.8X
Page 2: ......
Page 8: ...Summary...
Page 34: ...General Information 2 4 CFW501 2...
Page 38: ...About the CFW501 3 4 CFW501 3...
Page 42: ...HMI and Basic Programming 4 4 CFW501 4...
Page 58: ...Identification of the Inverter Model and Accessories 6 4 CFW501 6...
Page 72: ...Logical Command and Speed Reference 7 14 CFW501 7...
Page 76: ...Available Motor Control Types 8 4 CFW501 8...
Page 108: ...Functions Common to all the Control Modes 11 14 CFW501 11...
Page 134: ...Digital and Analog Inputs and Outputs 12 26 CFW501 12...
Page 148: ...Faults and Alarms 14 12 CFW501 14...