Digital and Analog Inputs and Outputs
CFW501 | 12-11
12
P0021 – Value of Frequency Input FI in %
Adjustable
Range:
-100.0 to 100.0 %
Factory
Setting:
Properties:
ro
Access groups
via HMI:
READ, I/O
Description:
This read-only parameter indicates the value of the frequency input in percentage of full scale. The indicated
values are those obtained after the offset action and multiplication by the gain. Check the description of
parameters P0247 to P0250.
P0022 – Value of Frequency Input FI in Hz
Adjustable
Range:
0 to 20000 Hz
Factory
Setting:
Properties:
ro
Access groups
via HMI:
READ, I/O
Description:
Value in hertz of the frequency input FI.
NOTE!
The operation of parameters P0021 and P0022, as well as of the frequency input, depends on the
activation of P0246.
P0246 – Frequency Input FI
Adjustable
Range:
0 = Inactive
1 = Active
Factory
Setting:
0
Properties:
Access groups
via HMI:
I/O
Description:
When in "1" this parameter activates the frequency input, making the digital input DI2 function in P0264 be
ignored, as well as the value of bit "1" of P0012 is maintained in "0". On the other hand, when in "0" the
frequency input is inactive keeping parameters P0021 and P022 in zero.
Summary of Contents for CFW501 V1.8X
Page 2: ......
Page 8: ...Summary...
Page 34: ...General Information 2 4 CFW501 2...
Page 38: ...About the CFW501 3 4 CFW501 3...
Page 42: ...HMI and Basic Programming 4 4 CFW501 4...
Page 58: ...Identification of the Inverter Model and Accessories 6 4 CFW501 6...
Page 72: ...Logical Command and Speed Reference 7 14 CFW501 7...
Page 76: ...Available Motor Control Types 8 4 CFW501 8...
Page 108: ...Functions Common to all the Control Modes 11 14 CFW501 11...
Page 134: ...Digital and Analog Inputs and Outputs 12 26 CFW501 12...
Page 148: ...Faults and Alarms 14 12 CFW501 14...