Functions Common to all the Control Modes
CFW501 | 11-7
11
U
d
rated
DC link voltage (P0004)
F0022-
Overvoltage
DC link
regulation
Time
Time
U
d
P0151
Output
speed
Figure 11.5:
Example graph of the DC ling voltage limitation – Accelerate Ramp (P0152 = 1 or P0152 = 3)
Like in the DC link voltage regulation, the output current regulation also has two operating modes: “Ramp
Holding” (P0150 = 2 or 3) and “Decelerate Ramp” (P0150 = 0 or 1). Both actuate limiting the torque and
power delivered to the motor, so as to prevent the shutting down of the inverter by overcurrent (F0070). This
situation often occurs when a load with high moment of inertia is accelerated or when short acceleration time
is programmed.
11.2.3 Output Current Limitation by “Ramp Hold” P0150 = 2 or 3
It prevents the motor from collapsing during torque overload in the acceleration or deceleration.
Actuation: if the motor current exceeds the value set in P0135 during acceleration or deceleration, the speed
will not be incremented (acceleration) or decremented (deceleration). When the motor current reaches a value
below P0135, the motor accelerates or decelerates again. Refer to
Figure 11.6: (a) and (b) Actuation modes of
current limitation via P0135 on page 11-8
.
It has a faster action than the “Decelerate Ramp” mode.
It acts in the motorization and regeneration modes.
11.2.4 Current Limitation Type “Decelerate Ramp” P0150 = 0 or 1
It prevents the motor from collapsing during torque overload in the acceleration or constant speed.
Actuation: if the motor current exceeds the value set in P0135, a null value is forced for the speed ramp input
forcing the motor deceleration. When the motor current reaches a value below P0135, the motor accelerates
again. Look at
Figure 11.6: (a) and (b) Actuation modes of current limitation via P0135 on page 11-8
.
Summary of Contents for CFW501 V1.8X
Page 2: ......
Page 8: ...Summary...
Page 34: ...General Information 2 4 CFW501 2...
Page 38: ...About the CFW501 3 4 CFW501 3...
Page 42: ...HMI and Basic Programming 4 4 CFW501 4...
Page 58: ...Identification of the Inverter Model and Accessories 6 4 CFW501 6...
Page 72: ...Logical Command and Speed Reference 7 14 CFW501 7...
Page 76: ...Available Motor Control Types 8 4 CFW501 8...
Page 108: ...Functions Common to all the Control Modes 11 14 CFW501 11...
Page 134: ...Digital and Analog Inputs and Outputs 12 26 CFW501 12...
Page 148: ...Faults and Alarms 14 12 CFW501 14...