Digital and Analog Inputs and Outputs
CFW500 | 12-23
12
NOTE!
The PTC input via DIx digital input does not detect short-circuits in the thermistor, but this resource is
available via analog input. Refer to
Section 15.3 MOTOR OVERTEMPERATURE PROTECTION (F0078)
v) MULTISPEED, ELECTRONIC POTENTIOMETER, FORWARD RUN/REVERSE RUN WITH 2
ND
RAMP
It combines the Multispeed, E.P. and Forward Run/Reverse Run with 2
nd
Ramp primary functions in the same
DIx digital input.
w) ACCELERATE E.P. - TURN ON / DECELERATE E.P. - TURN OFF
It consists of the Electronic Potentiometer function with capacity to enable the inverter by means of a pulse at the
start, and a pulse for the stop when the output speed is minimum (P0133).
DIx - Decelerate/
Turn OFF
Pulse
Turn ON
Pulse
Turn OFF
Time
Time
Time
P0133
(Fmin)
P0133
(Fmin)
P0134
(Fmax)
Inactive
Inactive
Active
Active
Output
frequency
DIx - Accelerate/
Turn ON
Figure 12.16:
Example of the Accelerate Turn ON / Decelerate Turn OFF
12.6 DIGITAL OUTPUTS
The CFW500 can operate up to five digital outputs according to the selected interface plug-in module; refer to
.
The DO1 digital output is always relay, while DO2 is always transistor; the other outputs can be relay or transistor
according to the plug-in module. On the other hand, the digital output parameter configuration makes no distinction
in this aspect, as detailed description below. Besides, the transistor digital outputs are always NPN, that is, in
open collector (sink).
P0013 – Digital Output Status DO5 to DO1
Adjustable
Range:
Bit 0 = DO1
Bit 1 = DO2
Bit 2 = DO3
Bit 3 = DO4
Bit 4 = DO5
Factory
Setting:
Properties:
ro
Access Groups
via HMI:
READ, I/O
Summary of Contents for CFW500 V1.8X
Page 2: ......
Page 4: ......
Page 8: ...Contents...
Page 34: ...General Information 2 4 CFW500...
Page 38: ...About the CFW500 3 4 CFW500 3...
Page 42: ...HMI and Basic Programming 4 4 CFW500 4...
Page 52: ...Programming Basic Instructions 5 10 CFW500 5...
Page 56: ...Identification of the Inverter Model and Accessories 6 4 CFW500 6...
Page 76: ...Available Motor Control Types 8 4 CFW500 8...
Page 84: ...V f Scalar Control 9 8 CFW500 9...
Page 170: ...Communication 17 8 CFW500 17...