INSTALLATION AND CONNECTION
3 INSTALLATION AND CONNECTION
3.1 MECHANICAL INSTALLATION
3.1.1 Environmental Conditions
Avoid:
Direct exposure to sunlight, rain, high humidity or sea-air.
Inflammable or corrosive gases or liquids.
Excessive vibration.
Dust, metallic particles or oil mist.
Environment conditions permitted for the operation of the inverter:
Temperature around the inverter: 0 °C(32 °F) up to the rated temperature indicated in
:
200V Line
: from 0 °C to 50 °C (32 °F to 122 °F).
400V Line
: from 0 °C to 40 °C (32 °F to 104 °F).
For temperatures surrounding the inverter higher than the specifications above, it is necessary to apply a 2 %
current derating for each degree Celsius (1.1 % for each degree Fahrenheit), limited to an increase of 10 °C (18
°F).
Air relative humidity: 5 % to 95 % non-condensing.
Maximum altitude: up to 1000 m (3.300 ft) - rated conditions.
From 1000 m to 4000 m (3.300 ft to 13.200 ft) - 1% of current derating for each 100 m (330 ft) above 1000 m
(3.300 ft) of altitude.
From 2000 m to 4000 m (6.600 ft to 13.200 ft) above sea level - maximum voltage derating (127 V / 240 V / 480 V,
according to the model, as indicated in
) of 1
.
1% for each 100 m (330 ft) above 2000 m
(6.600 ft).
Pollution degree: 2 (according to EN 50178 and UL 61800-5-1), with non-conductive pollution. Condensation
must not originate conduction through the accumulated residues.
3.1.2 Positioning and Mounting
The external dimensions and fixing holes, likewise the inverter net weight (mass) are shown in
.
Mount the inverter in the upright position on a flat and vertical surface. Allow the minimum clearances indicated in
, in order to allow the circulation of the cooling air. Do not install heat sensitive components
right above the inverter.
!
ATTENTION!
In order to comply with UL standard, use a cabinet with minimum dimensions of 150 % larger than
the product dimensions shown in
(the resulting clearance spaces arround
the inverter will be larger than those shown in
). For more details, refer to
3.2.3.1.1 Short Circuit Current Ratings (SCCR) on page 17
and to the
When installing two or more inverters vertically, respect the minimum clearance A + B (as shown in
) and provide an air deflecting plate so that the heat rising up from the lower
inverter does not affect the top inverter.
Provide independent condults for the physical separation of signal, control and power cables (refer
to
Section 3.2 ELECTRICAL INSTALLATION on page 13
12 | CFW320