P924 – Value for Low Level Alarm for the Control Process Variable
Adjustable
Range:
-99.99 a 99.99 [SoftPLC Eng. Un.]
Factory
Setting:
1.00
Properties:
Description:
This parameter defines the value below which the low level alarm will be generated for the control process variable
(A760).
NOTE!
Setting it to "0" disables the low level alarm and fault for the control process variable.
NOTE!
This parameter will be viewed according to the selection of the parameters for the SoftPLC engineering
unit (P510 and P511).
P925 – Time for Low Level Fault for the Control Process Variable (F761)
Adjustable
Range:
0.0 to 999.9 s
Factory
Setting:
0.0 s
Properties:
Description:
This parameter defines how long the low level alarm condition should remain so that the control process variable
(A760) will generate fault “F761: Low Level Fault of the Control Process Variable”.
NOTE!
Setting it to "0.0 s" disables the low level fault for the control process variable.
P926 – Value for High Level Alarm for the Control Process Variable
Adjustable
Range:
-99.99 a 99.99 [SoftPLC Eng. Un.]
Factory
Setting:
3.50
Properties:
Description:
This parameter defines the value above which the high level alarm will be generated for the control process
variable (A762).
NOTE!
Setting it to "0" disables the high level alarm and fault for the control process variable.
NOTE!
This parameter will be viewed according to the selection of the parameters for the SoftPLC engineering
unit (P510 and P511).
Summary of Contents for CFW300 V1.3X
Page 2: ......
Page 8: ...Contents...
Page 46: ...Identification of the Inverter Model and Accessories 6 4 CFW300 6...
Page 60: ...Logical Command and Speed Reference 7 14 CFW300 7...
Page 72: ...V f Scalar Control 9 10 CFW300 9...
Page 80: ...VVW Vector Control 10 8 CFW300 10...
Page 116: ...Digital and Analog Inputs and Outputs 12 24 CFW300 12...
Page 132: ...Reading Parameters 15 6 CFW300 15...