16-15
16
Read Only Parameters [09]
P0096 – DIx Status at the Moment of the Last Fault
Adjustable
Range:
Bit 0 = DI1
Bit 1 = DI2
Bit 2 = DI3
Bit 3 = DI4
Bit 4 = DI5
Bit 5 = DI6
Bit 6 = DI7
Bit 7 = DI8
Factory
Setting:
Properties:
RO
Access groups
via HMI:
08 FAULT HISTORY
Description:
It indicates the state of the digital inputs at the moment of the last fault occurrence.
The indication is done by means of an hexadecimal code, which when converted to binary will indicate the states
"active" and "inactive" of the inputs through numbers 1 and 0.
Example: If the code presented for the parameter P0096 on the keypad (HMI) is 00A5, it will correspond to the
sequence
10100101
, indicating that the inputs 8, 6, 3 and 1 were active at the moment of the last fault
occurrence.
Table 16.2 -
Example of correspondence between the P0096 hexadecimal code and the DIx states
0
0
A
5
0
0
0
0
0
0
0
0
1
0
1
0
0
1
0
1
No relation with the DIx
(always zero)
DI8
Active
(+24 V)
DI7
Inactive
(0 V)
DI6
Active
(+24 V)
DI5
Inactive
(0 V)
DI4
Inactive
(0 V)
DI3
Active
(+24 V)
DI2
Inactive
(0 V)
DI1
Active
(+24 V)
P0097 – DOx Status at the Moment of the Last Fault
Adjustable
Range:
Bit 0 = DO1
Bit 1 = DO2
Bit 2 = DO3
Bit 3 = DO4
Bit 4 = DO5
Factory
Setting:
Properties:
RO
Access groups
via HMI:
08 FAULT HISTORY
Description:
It indicates the state of the digital outputs at the moment of the last fault occurrence.
The indication is done by means of an hexadecimal code, which when converted to binary will indicate the states
"active" and "inactive" of the outputs through numbers 1 and 0.
Example: If the code presented for the parameter P0097 on the keypad (HMI) is 001C, it will correspond to the
sequence
00011100
, indicating that the outputs 5, 4, and 3 were active at the moment of the last fault
occurrence.
Table 16.3 -
Example of correspondence between the P0097 hexadecimal code and the DOx states
0
0
1
C
0
0
0
0
0
0
0
0
0
0
0
1
1
1
0
0
No relation with the DOx
(always zero)
No relation with the DOx
(always zero)
DO5
Active
(+24 V)
DO4
Active
(+24 V)
DO3
Active
(+24 V)
DO2
Inactive
(0 V)
DO1
Inactive
(0 V)
Summary of Contents for CFW-11 Series
Page 2: ......
Page 54: ...2 4 2 General Information ...
Page 58: ...About the CFW 11 3 3 4 ...
Page 74: ...Inverter Model and Accessories Identification 5 14 6 ...
Page 86: ...Inverter Model and Accessories Identification 6 12 6 ...
Page 94: ...Available Control Types 8 2 8 ...
Page 118: ...VVW Control 10 8 10 ...
Page 182: ...Functions Common to All the Control Modes 12 26 12 ...
Page 220: ...Dynamic Braking 14 4 14 ...