S STATUS
4 S STATUS
Allows viewing of the SSW reading variables.
S5 COMMUNICATIONS
HMI monitoring parameters of the communication interfaces.
For a detailed description, refer to the Modbus RTU and Anybus User’s Manuals of the SSW according to the interface
used.
S5.1 Status Word
.1 SSW
0 ... 15 Bit
Description:
Word of SSW status.
.1 SSW
Word of SSW status.
Bit
Value/Description
Bit 0
Running
0: The motor is not enabled.
1: The motor is enabled.
Bit 1
Gener. Enabled
0: When it is general disabled by any mean.
1: When it is general enabled by all the means.
Bit 2
JOG
0: The JOG function is inactive.
1: The JOG function is active.
Bit 3
Initial Test
0: None.
1: During the initial tests before the motor starting.
Bit 4
Ramp Up
0: It is not accelerating.
1: During the whole acceleration.
Bit 5
Full Voltage
0: There is no full voltage applied to the motor.
1: Full voltage is being applied to the motor.
Bit 6
Bypass
0: With open bypass.
1: With closed bypass.
Bit 7
Ramp Down
0: It is not decelerating.
1: During the whole deceleration.
Bit 8
Remote
0: Local.
1: Remote.
Bit 9
Braking
0: It is not executing braking.
1: During the braking process.
Bit 10
FWD/REV
0: It is not reverting the rotation direction.
1: During the rotation reversion process.
Bit 11
Reverse
0: Forward rotation.
1: Reverse rotation.
Bit 12
Ton
0: None.
1: Time before start (C5.7.2).
Bit 13
Toff
0: None.
1: Time after stop (C5.7.3).
Bit 14
Alarm
0: The SSW is not in alarm condition.
1: The SSW is in alarm condition.
Note: The active alarm codes can be read by means of the menu D2.1.
Bit 15
Fault
0: The SSW is not in fault condition.
1: The SSW is in fault condition.
Note: The active fault code can be read by means of the menu D1.1.
S5.2 Command Word
.5 Slot1
0 ... 15 Bit
.6 Slot2
0 ... 15 Bit
SSW900 | 12