LX3V-4AD
8
WECON TECHNOLOGY CO., LTD.
Offset is the “Position” of the calibrated line, identified at a digital value of 0.
(d) Negative offset.
(e) Zero offset: Default is 0V or 4mA.
(f) Positive offset.
Offset and gain can be set independently or together. Reasonable offset ranges are -5 to +5V or
-20mA to 20mA, and gain values 1V to 15V or 4mA to 32mA. Gain and offset can be adjusted by
software in the LX3V main unit (please refer to program example 2).
Bit device’s b1, b2 of the gain/offset BFM #21 should be set to 0, 1 to allow adjustment.
Once adjustment is complete these bit devices should be set to 1, 0 to prohibit any further
changes.
Channel initialization (BFM #0) should be set to the nearest range, i. e. voltage/current etc.
6.
Example program
6.1 basic program
In the following example channels CH1 and CH2 are used as voltage inputs. The LX3V-4AD block is
connected at the position of special function block No.0. Averaging is set at 4 and data registers D0
and D1 of the PC receive the averaged digital data.