Check that the LX3V system configuration rules have not been broken, i.e. the number of
special function blocks does not exceed 8 and the total system I/O is equal or less than 256 I/O.
3)
Ensure that the correct operating range has been selected for the application.
4)
Check that there is no power overload on either the 5V or 24V power sources, remember the
loading on a LX3V main unit or a powered extension unit varies according to the number of
extension blocks or special function blocks connected.
5)
Put the LX3V main unit into RUN.
7.2 Error checking
If the LX3V-4AD special function block does not seem to operate normally, check the following
items.
Check the status of the POWER LED.
Lit: The extension cable is properly connected.
Otherwise: Check the connection of the extension cable.
Check the external wiring.
Check the status of the “24V” LED (top right corner of the LX3V-4AD).
Lit: LX3V-4AD is OK; 24V DC power source is OK.
Otherwise: Possible 24VDC power failure, if OK possible LX3V-4AD failure.
Check the status of the “A/D” LED (top right corner of the LX3V-4AD).
Lit: A/D conversion is proceeding normally.
Otherwise: Check buffer memory #29 (error status). If any bits (b2 and b3) are ON, then this is
why the A/D LED is OFF.