Surge Protection

This product features built-in surge protection circuitry in compliance with 

applicable standards.

For comprehensive protection of a luminaire installation against lightning and  

electrical surges, it is essential to cover mains supply and data input lines at  

the distribution board level, by using respective primary (Type 1) and secondary  

(Type 2) surge arrestors in compliance with EN61643-11/IEC61643-1.

Warning

Ensure that all required surge protection measures are in place and activated  

prior to luminaire installation. Also, disconnect luminaires before operating 

high-power devices such as, for example, electrical arc welders.

Do not open during installation

This product is factory-sealed. 

Refer to the instructions contained in this 

document for details.

WE-EF LEUCHTEN

Installation and Maintenance

Instructions 

Bracket Mounted Floodlight

FLB141 #4 LED

Summary of Contents for FLB141 4 LED

Page 1: ...ype 1 and secondary Type 2 surge arrestors in compliance with EN61643 11 IEC61643 1 Warning Ensure that all required surge protection measures are in place and activated prior to luminaire installatio...

Page 2: ...1 IP66 IK08 Class I ta 40 C Bracket Mounted Floodlight FLB141 4 800 1 7 5 x 2 1 5 140 Weight kg for FLB141 4 LED 6 8 Windage area m for FLB141 4 LED 0 095 Orientation horizontal...

Page 3: ...ecial maintenance work is required Do not use high pressure cleaners In case of component failure due to abnormal circumstances or at end of life replacement must be carried out E D VXLWDEO TXDOL HG D...

Page 4: ...alling and connecting the luminaire Notice I WKH OXPLQDLUH LV PRGL HG E DQ ERG RWKHU than the original manufacturer then the warranty will no longer be valid and shall become the full respon sibility...

Page 5: ...F Warning Ensure not to damage any electrical cable water pipe or other items drilling holes 5HPRYH PRXQWLQJ DQJH A by loosening screws B Detach terminal connector C 3 Check that rating shown on lumin...

Page 6: ...L Phase N Neutral Earthing b 1 10 V DALI L Phase N Neutral Earthing DA DA DALI control line D D 1 10 V control line 8 Ensure that all surfaces are clean and dry 3RVLWLRQ OXPLQDLUH RYHU PRXQWLQJ DQJH...

Page 7: ...luminaire in desired direction retighten screws M and N Attention The luminaire is pre assembled for downward lighting applications as illustrated To aim upwards loosen screws P and rotate head assem...

Page 8: ...fo switzerland we ef com WE EF LIGHTING United Kingdom Tel 44 844 880 5346 Fax 44 844 880 5347 info uk we ef com WE EF LIGHTING Thailand Tel 66 2 738 9610 Fax 66 2 175 2174 LQIR DVLDSDFL F ZH HI FRP W...

Reviews: