LMDW-101/102

Digital Lighting Management

Dual Technology Occupancy Sensor

COVERAGE PATTERN

Do not obstruct the lens.

40 ft

40 ft

25 ft

25 ft

TOP

VIEW

180°

Major motion
Minor motion

Major motion
Minor motion

PIR

Coverage

Ultrasonic

Coverage

4 ft

SIDE

VIEW

25 ft

40 ft

5 ft

30

(9.1m)

20

(6.1m)

35 ft

35 ft

Quick St

art Guide

Line

Voltage

Room

Controller

J-Boxes

Daylight Sensor

Switch

LMDW-101

Switch

Corner Mount

Sensor

Ceiling Mount

Sensor

DLM Local Network

Low Voltage

LMRJ Cables

Loads

2

1

Line/Hot

Black wire

Neutral

White wire

Red wire

to Load A (1)

Yellow wire

to Load B (2)

LMRC

102

Room

Controller

J Box

Corner Mount

Occupancy

Sensor

LMDW

Sensor

Switch

To

Load/Line

(Class 1 wiring)

DLM Local Network 

(low voltage, Class 2)

LMRJ Cables

Voltage  ................................................................................24VDC
Current Consumption .......................................................... 20mA
Power Supply .............. Watt Stopper/Legrand Room Controllers
Connection to the DLM Local Network ...................2 RJ-45 ports
DLM Local Network Characteristics: 

  Provides low voltage power over Cat 5e cable (LMRJ). 

  Supports up to 24 communicating devices, including 4  

  LMRC-10x or LMPL-101 max per each DLM Local Network. 

  Free topology up to 1,000ft of low voltage cable.
Environment ................................................. For Indoor Use Only
  Operating Temperature ....................32° to 131°F (0° to 55°C)
  Storage Temperature ...................... 23° to 176°F (-5° to 80°C)
  Relative Humidity ...........................5 to 95% (non condensing)
Patent Pending

This unit is pre-set for Plug n’ Go operation, 

adjustment is optional.

For full operational details, adjustment and more 
features of the product, see the DLM System Installation 
Guide provided with the DLM room controllers and also 
available at

 

www.wattstopper.com

CONNECTIVITY

The illustrations below show examples of free-topology wiring. The LMDW communicates 

to all other Digital Lighting Management devices connected to the low voltage DLM Local 

Network, regardless of their position on the DLM Local Network. 

Installation shall be in accordance with all applicable 

regulations, local and NEC codes.
To be connected to a Class 2 power source only.
Class 2 Device Wiring Only – Do Not Reclassify and Install
as Class 1, 3 or Power and Lighting Wiring.
Wire connections shall be rated suitable for the wire 

size (lead and building wiring) employed.
Do not apply cleaning solvent directly onto unit. Apply cleaning 

solvent onto a cloth, then wipe the unit to clean it.

MOUNTING

WARNING:

 Do Not Install To Cover a 

Junction Box Having Class 1, 3 or Power 

and Lighting Circuits.

Note: Plus 10

°

 above horizon.

BUTTONS AND INDICATORS

Up

Down

Select

Configure

PIR Lens

Lens release

Button LED

IR Window

LMDW-101

PIR Detection LED
Ultrasonic Detection LED/
Sensor Binding LED

       Button

       On/Off

LMDW-101

LMDW-102