EN
4
VB25-32-IM-DE-W-UK-05-2023-Rev.1 | Part no. 10025989
3 Technical data
Hydraulic performance data
VB25/32-2
VB25/32-3
VB25/32-4
VB25/32-5
Max. operating pressure
6 bar
Operating temperature
2 °C to 110 °C
Media
Water / water-glycol mixtures according to VDI 2035/ÖNORM H 5195
Dimensions
Width x height x depth
with EPP shell
600 x 178 x 137 mm
900 x 178 x 137 mm
1200 x 178 x 137 mm
1500 x 178 x 137 mm
Width x height x depth
without EPP shell
510 x 157 x 80 mm
810 x 157 x 80 mm
1110 x 157 x 80 mm
1410 x 157 x 80 mm
Total weight
excluding packaging
5.6 kg
8.4 kg
12.4 kg
16.5 kg
including packaging
5.9 kg
8.8 kg
13.2 kg
17.4 kg
Connections to pipe net-
work
Heating circuit
G 1 ½ union nut, flat sealing
Boiler circuit
G 1 ½ male connection. flat sealing
Nominal diameter
DN 32
Materials
Manifold
tubular steel
Union nut
brass CW617N
End cap
brass CW617N
Flat seal
AFM 34/2
Insulation
EPP
Flow coefficient (Cv) values
1 outlet open
15.2 m³/h
13.8 m³/h
14.8 m³/h
12.3 m³/h
2 outlets open
20.1 m³/h
19.1 m³/h
21.2 m³/h
19.3 m³/h
3 outlets open
-
20.6 m³/h
24.0 m³/h
21.8 m³/h
4 outlets open
-
-
24.1 m³/h
23.0 m³/h
5 outlets open
-
-
-
23.5 m³/h