HydroGuard® Series LFG480 and LFE480 

Lavatory Tempering Valve

Installation Instructions

IS-P-G480_E480

Approval 

n

Description 

n

Powers Series LFG480 & LFE480 are designed for lavatory 

applications where the temperature of the hot water must be 

controlled for safe, economic use.  An advanced thermal actua-

tor quickly senses and compensate for outlet temperature fluc-

tuations induced by water temperature and pressure changes in 

the supply line.

Specifications 

n

Maximum Operating Pressure:  ............................ 125psi (861 kpa)
Maximum Hot Water Temperature:  ........................... 180°F (82°C)
Minimum Hot Water Supply Temp.:  ....  5°F (3°C) Above Set Point**
Hot Water Inlet Temperature Range:  ......... 120 – 180°F (49-82°C)
Cold Water Inlet Temperature Range:  .............. 40 – 80°F (4-27°C)
Temperature Adjustment Range:  ................. 80 – 120°F (27-49°C)
Minimum Flow: 
  

LFG480  ..................................................  0.25 gpm (1.0 lpm)

  

LFE480  ..................................................  0.50 gpm (1.9 lpm)

Listing:  ................. ASSE 1070, IAPMO cUPC, and NSF 61-9 & 372

** With Equal Pressure

Flow Capacity 

n

LFE480-00Q

LFE480-10Q

WARNING

!

Read this Manual BEFORE using this equipment.
Failure to read and follow all safety and use infor-

mation can result in death, serious personal injury, 

property damage, or damage to the equipment.
Keep this Manual for future reference.

You are required to consult the local building and plumbing 

codes prior to installation. If the information in this manual is 

not consistent with local building or plumbing codes, the local 

codes should be followed. Inquire with governing authorities 

for additional local requirements.

WARNING

!

FAILURE TO COMPLY WITH PROPER INSTALLATION AND 

MAINTENANCE INSTRUCTIONS COULD CONTRIBUTE TO 

THE VALVE FAILURE, RESULTING IN INJURY AND/OR 

DEATH.
TO ENSURE THE ACCURATE AND RELIABLE OPERATION OF 

THIS PRODUCT, IT IS ESSENTIAL TO:

•    Properly design the system to minimize pressure and 

temperature variations.

•    This valve is factory preset. However, it can be adjusted 

to deliver scalding temperatures. 

Check outlet tem-

perature to ensure it does not exceed 105°F (41°C).

 

Make sure temperature limit stop is properly re-set to 

maximum 105°F (41°C) following valve maintenance or 

repair. Tampering with limit stop in any way may result 

in scalding temperature causing serious bodily harm and/

or death.

WARNING

!

WARNING

!

Need for Periodic Inspection and Yearly Maintenance: 

 

Periodic inspection and yearly maintenance by a licensed con-

tractor is required. Corrosive water conditions, inlet temperatures 

over 200°F (93°C), and/or unauthorized adjustments or repair 

could render the valve ineffective for service intended. Regular 

checking and cleaning of the valve’s internal components and 

check stops helps assure maximum life and proper product 

function. Frequency of cleaning and inspection depends upon 

local water conditions.

PSI

M

0  10 20  30 40 50 60  70 80 90 100

0

E480

G480

Certified to

NSF/ANSI/CAN 61-9 & 372

ASSE 1070

This product meets the reduced Q test statistic criteria of  

0.5 ppb for lead per Section 9.5.1.1 of NSF/ANSI/CAN 61.