LYNC UV-H
SECTION 4: INSTALLATION INSTRUCTIONS
•
•
•
Figure 4-1
4.1.3 Other Materials Needed
The Lync UV-H unit requires four #12 to 1/4
” diameter fasteners (not provided) to mount to a wall. Pipe
insulation is recommended for any overhead piping to prevent condensation from dripping onto unit.
The unit also requires a drain for the purge valve discharge line.
WARNING! Use copper or stainless steel piping at the UV outlet since water temperatures can reach 176
°
F
(80
°
C) if the UV unit operates without water flow or the ability to purge. DO NOT USE PVC.
These fittings, pipe insulation, and any piping compatible with the plumbing should be on hand before
you begin installation. See Figure 4.2 and make a list of all necessary components including solder, paste
and thread sealant. Bypass piping and valves that isolate the unit are optional, (but recommended) as is
a drain valve for draining the unit.