Lync AEGIS
4: HYDRAULIC CONNECTION
L-OMM-012_A
•
4/20/2022
Technical Support • (800) 433-5654 • Mon-Fri, 8 am - 5 pm EST
22
of
37
4.5. Condensate Disposal
The Aegis A is equipped with two condensate drain pipes per air coil (2 for Aegis A 250, 4 for Aegis A
350-500). This allows for the proper disposal of condensate after a defrost cycle. This condensate must
be piped to a drain. In the case of freezing conditions, condensate piping must be insulated and/or
wrapped with a heating coil to prevent condensate freezing in the piping.
Figure 8: Condensate Drain Pipes