“ RF init ”
Wireless outside temperature probe
1.
INSTRUCTION
- The probe must be placed on the wall with the enclosed screws, or otherwise if the support is
not appropriated.
- It must be vertically installed as indicated on the installation scheme (holes allowing air
circulation down).
Once fixed on the wall, don’t forget to put the rubber caps provided to ensure the tightness of
the box against dripping water.
- the probe must be preferably placed on a north or north/west wall sheltered for weather and
away from parasites of heat sources such suction, exhaust air of the building, …
2.
RF INITIALISATION & BATTERY REPLACEMENT
To initialize your RF outside probe with your control system, make sure that it is properly
configured to work with an RF probe.
- Then, place your control system in «
RF init
» mode (see the instruction manual of the control
system)
- Remove the protector film of the battery
- Then switch on the RF probe (pointing up) : the status led blinks green
- Check on your control system the good reception of the signal
- If the configuration unfolds as it should, close the box of the RF probe
- If the configuration doesn’t unfold as it should, try to place the antenna of the control system
as close as possible of the RF probe.
3.
TECHNICAL CARACTERISTICS
Operating temperature
-10°C to 55°C
Power supply
Operating life
2 AAA (LR03)
~ 5 years
Radio Frequency
433.92 MHz <10mW.
Range of approximately 180m in open space.
Range of approximately 30m in residential environment
Homologations
EN 300220-1, -2 / EN 301489-1, -3
R&TTE
Electrical protection
IP 45
Status LED
Blinking green (flash 10sec)
RF initialization
4.
Battery replacement
- Switch off your RF probe
- Take off the used batteries (Do not throw your batteries in the trash, recycle as it should be)
- Put the new batteries (always replace the 2 batteries in the same time)
- Switch ON your probe (pointing up), the led status blinks green.
- Close the box
ON
52mm
80mm
80mm
OFF
ON
OFF
ON
OFF
ON