Centurion Water Heater- Edge [ii]: Install-Operation-Service
SECTION 4: START SEQUENCE
OMM-0153_A
• 8/25/2022 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page 41 of 131
4.3 START/STOP LEVELS
– AIR/FUEL & ENERGY INPUT
The table below shows the relationship between the energy input and Air/Fuel Valve position for
the models covered in this document.
CEN2000 Air/Fuel Valve Position
NATURAL GAS
Air/Fuel Valve Position
(% Open)
Energy Input
(Btu/Hr)
Water Heater Energy Input
(% Of Full Capacity)
18% (Stop Level)
100,000 (29.3 kW)
5%
30%
310,000 (90.9 kW)
16%
40%
540,000 (158.3 kW)
27%
50%
770 ,000 (225.7 kW)
39%
60%
1,030,000 (301.9 kW)
52%
70%
1,290,000 (378.1 kW)
65%
80%
1,560,000 (457.2 kW)
78%
90%
1,840,000 (539.3 kW)
92%
100%
2,000,000 (586.0 kW)
100%