10.21 Condensate Trap and Neutralizing Reservoir Maintenance
The condensate trap and neutralizing reservoir must be checked every year and cleaned if
required. Follow the steps below to properly inspect, refill or replace the condensate neutralizing
reservoir and media:
Monitor the level of the neutralization media in the reservoir periodically. The pH can be
checked after the
condensate has exited from pipe “A” of Figure 4-8. Check the pH level every
three months for the first year. Use a suitable pH test strip paper or an electronic pH meter for
precise measurement. The frequency of pH level inspection can be reduced to every six months
or every year depending on the readings obtained compared to local water authority
requirements. The neutralizing media should be replaced when the pH level drops below the
minimum level of the local water authority. For replacement media contact AERCO.
To inspect and maintain the condensate system, perform the following:
Condensate System Inspection and Maintenance
1.
Turn off electrical power to the unit.
2.
Close the manual gas shut-off valve (Figure 7-1).
3.
Follow the steps in Section 10.14 to remove the lower front cover.
4.
Pull out the condensate collection tank assembly
“A” (Figure 10-9).
Figure 10-9: Pull Out Tank Figure 10-10: Open Cover
5.
Open the neutralizer tank
cover “C” per Figure 10-10, and inspect the collection tank for
wear or damage.
6.
Examine the neutralizing media and replenish with fresh media if needed.
7.
Fill the condensate collection tank with fresh water until the water begins to flow from the
condensate drain piping.