Edge [ii] Controller Operation Manual
SECTION 4: DIAGNOSTICS
OMM-139_E
• 8/25/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
79
of
196
Figure 4.3: Diagnostics: Analog Outputs and Relays Screen
2. Press either
Relays
or
Analog Outputs
.
NOTE:
You can navigate between the
Analog Output
and
Relays
screens in round-robin fashion
using the
Page Left
and
Page Right
icons on both screens.
4.3.1 Relays
The Relays screen displays a list of all relays in the system and allows you to manually test
each one individually to confirm they are functioning. Complete the instructions below to test the
unit’s relays.
1. Go to:
Main Menu
→
Diagnostics
→
Analog Outputs and Relays
→
Relays
.
Figure 4.3.1: Analog Outputs and Relays: Relays Screens
2. Press the relay you want to test; it turns green, enabling it for 1 minute, after which it is
automatically disabled. You can select multiple relays to test at one time.
3. During the test period, verify that the function associated with the selected relay(s) occurred
as expected.
4. The Relay test will disable automatically after 1 minute.