Edge [ii] Controller Operation Manual
SECTION 2: EZ SETUP
OMM-139_E
• 8/25/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
41
of
196
Figure 2.3.2.1.3-5: BST Manager
– Other: Other Analog Input Screen
B. If you chose
Network
, the
Select BAS Mode
EZ Setup: BST Manager
–
Two Applications
Complete the instructions in
one
of the three Sections below on the BST Manager if the unit
was configured to run
two
application. If it will run a single application, see Section 2.3.2.1.
2.3.2.2.1
EZ Setup: BST Manager
–
Space Heating and DHW Applications
Complete the instructions below only if you chose
both
Space Heating
and
DHW
at the end of
Section 2.3.2.
Figure 2.3.2.2.1-1: BST Manager
– SH & DHW: Select Your Boiler Application
1. When both
Domestic Hot Water
and
Space Heating
applications are chosen, Domestic
Hot Water priority mode is automatically activated and the
DHW Priority
screen appears (a
green border appears on the previous choice, if there was one). Set
DHW Priority Mode
to one of the following then press
Next
to continue. (Note, your choice will affect which
options appear in Step 10, below.)
•
1 Swing Valve
•
2 Swing Valves
•
Setpoint Boost