Edge [ii] Controller Operation Manual
SECTION 6
– ADVANCED SETUP
OMM-139_E
• 8/25/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
164
of
196
Purge Control
The
Purge Control
screen contains parameters associated with the purge process for this unit.
1. Go to:
Main Menu
→
Advanced Setup
→
Performance
→
Fire Control
→
Purge Control
.
Figure 6.6.3.1: Fire Control: Purge Control
2. This screen includes the following parameters:
•
Purge Blower Voltage
: Allows adjustment of the blower speed (blower output
voltage) during the Purge cycle. (Range: 2.0 to 10.0 V)
•
Purge Timer
: Allows adjustment of the pre-ignition purge time. (Range: 5 to 60 sec.)
•
Post Purge Timer
: Allows adjustment of the purge time when a unit shuts down.
(Range: 0 to 60 sec.)
Ignition Control
The
Ignition Control
screen displays parameters related to ignition that apply to this unit only.
1. Go to:
Main Menu
→
Advanced Setup
→
Performance
→
Fire Control
→
Ignition
Control
.
Figure 6.6.3.2: Fire Control: Ignition Control
2. The following ignition control parameters are available: