Edge [ii] Controller Operation Manual
SECTION 6
– ADVANCED SETUP
OMM-139_E
• 8/25/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
163
of
196
o
Setpoint Limit Band
: (If
Setpoint Limiting
=
Enabled
): Sets the number of
degrees
below
Setpoint High Limit
the unit’s outlet temperature must fall before the
unit restarts (Default = 5°F (2.8°C), Range = 0°F to 10°F (0°C to 5.5°C))
4. The
Setback
Setpoint
features can be used to lower the Setpoint during periods when a
lower Setpoint is appropriate, such as at night. To enable this feature, set
Setback
Schedule
to
Enabled
, then
configure the following additional parameters:
•
Setback Setpoint
: The Setpoint that will be in effect during the Setback period.
•
Setback Start Time
: The
Setback
period’s
start
time (example: 11:00 PM). This
parameter also appears in
•
Setback Stop Time
: The
Setback
period’s
end
time (example: 5:00 AM).
6.6.3 Fire Control
The
Fire Control
screen provides access to functionality that affect the firing of this unit. All four
controls apply to this unit only.
1. Go to:
Main Menu
→
Advanced Setup
→
Performance
→
Fire Control
.
Figure 6.6.3: Performance: Fire Control
NOTE:
You can navigate from one
Fire Control
screen to the next in round-robin fashion using the
Page Left
and
Page Right
icons on each screen.