Edge [ii] Controller Operation Manual
SECTION 6
– ADVANCED SETUP
OMM-139_E
• 8/25/2020 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
150
of
196
DHCP Enabled
DHCP Disabled
Figure 6.4.4: Comm & Network: Ethernet Screen
2. If
DHCP
is
Disabled
, manually enter the communication parameters, typically provided by a
network administrator, in the following parameters:
•
IP Address
•
Subnet
•
Gateway
•
DNS 1
•
DNS 2
3. If
ICMP Ping
is
Enabled
, the unit will respond to a ping from a network administrator.
6.4.5 Communication Failsafe
The
Communication Failsafe
option specifies how the unit will operate when either the
Manager communication or a Remote Signal is lost and the unit has to operate independently.
1. Go to:
Main Menu
→
Advanced Setup
→
Comm & Network
→
Communication Failsafe
.
Figure 6.4.5: Comm & Network: Communication Failsafe Screen
2. Set the
Failsafe Mode
parameter to either
Constant Setpoint
or
Shutdown
.
•
If you chose
Constant Setpoint
, one additional parameter appears:
o
Unit Failsafe Setpoint
: Set it
to the unit’s default setpoint if
communication fails.