Series 9DM2, 9DM3

Dual Check with Atmospheric Vent

Sizes: 

1

2

", 

3

4

" (15, 20mm)

                           Model 9DS- Remove union connections before sweating

•  The 9D Dual Check with Atmospheric Vent is designed for use on non-health hazard, 

continuous pressure, point of use applications for protection against backsiphonage 

and backpressure. Install in accordance with the local codes.

•  For the best system performance, install on the fresh water feed line before any pres-

sure regulators (such as the Watts Series 1156 on a residential boiler application).

•  Flush the line before installing the unit to remove any solder, flux or pipe chips. Clean 

the strainer every six months or as conditions require.

•  Some discharge is expected, particularly on start-up, until all seating surfaces seal. 

Continuous discharge is an indication that the internal seating parts and surfaces may 

require the cleaning.

• May be installed horizontally or vertically.
•  Quick closing valves, water hammer or supply pressure fluctuations can cause inter-

mittent discharge. The installation of a Water Hammer Arrestors (Watts Series 05) or 

Water Pressure Regulator (Watts Series 1156 or 25AUB) may be required to correct 

the problem.

 

NOTICE

It is important not to install where the 

discharge could cause damage. Pipe 

the discharge line in accordance with 

local code requirements. A physical air 

gap must be maintained between the 

discharge pipe and the drain or sump. 

Create the air gap by cutting the pipe 

on a 45° bevel, at a distance of 12" 

above the floor. If used on boiler appli-

cations do not use an air gap fitting 

at face level so as to prevent personal 

injury from scalding water or steam. In 

no event should the vent opening or drain line be plugged.
•  If local codes require the device be tested, it must be installed as shown in  

the drawing on the reverse side.

RP/IS-9D

9D Total Repair Kits

EDP No.

KiT No.

SizE

0886010

RK 9DM2 T

1

2

", 

3

4

" (15, 20mm)

0886011

RK 9DM3T

1

2

" (15mm)

Kit includes: primary & secondary checks, seat 

and two union seals.

Boiler installation

Watts 9DM3 Heating System Installation

Supply

Boiler

Return

Vent

Drain

Floor Drain

Integral 

Strainer

Watts Model 1156F Feed 

Valve with Union

Watts 

9DM3 

WARNING

!

Read this Manual BEFoRE using this equipment.
Failure to read and follow all safety and use information can 

result in death, serious personal injury, property damage, or 

damage to the equipment.
Keep this Manual for future reference.

NOTICE

Inquire with Governing Authorities for Local 

Installation Requirements