background image

ProtoNode FPC-N34 & FPC-N35 User Manual

 

CHAPTER 5 

– Setup Web Server Security 

 

 

OMM-0150_B    

•    5/20/2021                     Technical Support  •  (800) 526-0288  •  Mon-Fri, 8 am - 5 pm EST                     Page 

37

  of 

140

 

 

5.2  Select the Security Mode 

On the first login to the FieldServer, the following screen will appear that allows the user to 
select which mode the FieldServer should use. 

 

Figure 5-5: Security Mode Selection Screen 

NOTES: 

Cookies are used for authentication. 

To change the web server security mode after initial setup, go to Section 5.6 

The sections that follow include instructions for assigning the different security modes. 

 

5.2.1  HTTPS with Own Trusted TLS Certificate 

This is the recommended selection and the most secure. Please contact your IT department to 
find out if you can obtain a TLS certificate from your company before proceeding with the Own 
Trusted TLS Certificate option. 

Once this option is selected, the Certificate, Private Key and Private Key Passphrase fields will 
appear under the mode selection. 

Summary of Contents for 64168

Page 1: ...AERCO com Technical Support 800 526 0288 Mon Fri 8 am 5 pm EST 2021 AERCO Disclaimer The information contained in this manual is subject to change without notice from AERCO International Inc AERCO makes no warranty of any kind with respect to this material including but not limited to implied warranties of merchantability and fitness for a particular application AERCO International is not liable f...

Page 2: ...net features claimed in the listing The mark is a symbol of a high quality BACnet product Go to http www BACnetInternational net btl for more information about the BACnet Testing Laboratory Click here for BACnet PIC Statement LonMark International is the recognized authority for certification education and promotion of interoperability standards for the benefit of manufacturers integrators and end...

Page 3: ...4 BACnet MS TP or Modbus RTU FPC N34 Setting the Baud Rate for BAS Network 16 CHAPTER 3 Interfacing ProtoNode to Devices 17 3 1 ProtoNode FPC N34 and FPC N35 Showing Connection Ports 17 3 2 Device Connections to ProtoNode 19 3 2 1 Biasing the Modbus RS 485 Device Network 20 3 2 2 End of Line Termination Jumper for the Modbus RS 485 Device Network 21 3 3 BACnet MS TP Modbus RTU or Metasys N2 FPC N3...

Page 4: ...Heater Management System WHM and On Board Boiler Sequencing Technology BST Point Definitions 63 Appendix B 5 AM Series Point Definitions 67 Appendix C AERCO EQUIPMENT POINT MAPPINGS 71 Appendix C 1 AM Mngr Modbus RTU Mappings to BACnet MS TP BACnet IP Metasys N2 Modbus TCP IP and LonWorks 71 Single Node Option 71 Appendix C 2 AM Dep Modbus RTU Mappings to BACnet MS TP BACnet IP Metasys N2 Modbus T...

Page 5: ...ES FOR MODULEX E8 CONTROLLER 125 Appendix H 1 BCM and BMM Fault Code Conversion Table 125 Appendix H 2 BMM Fault Code Table 126 Appendix H 3 BCM Fault Code Table 128 Appendix I AM ERROR STATE AND STATUS TABLES 131 Appendix I 1 AM Lockout Error Codes Table 131 Appendix I 2 AM Blocking Error Codes Table 132 Appendix I 3 AM State Parameters Table 133 Appendix I 4 AM Status Parameters Table 133 Append...

Page 6: ... BACnet IP FPC N34 Set the BACnet Device Instance 2 5 2 7 Metasys N2 Modbus RTU or Modbus TCP IP FPC N34 Set the Node ID 2 5 3 8 BACnet MS TP or Modbus RTU FPC N34 Set the BAUD rate of the Field Protocol on DIP Switch Bank B 2 5 4 9 Connect ProtoNode s 6 pin RS 485 connector to the Modbus RS 485 network that is connected to each of the devices 3 2 10 Connect ProtoNode FPC N34 s 3 pin RS 485 port t...

Page 7: ... MS TP BACnet IP Metasys 2 N2 by JCI Modbus RTU Modbus TCP IP or LonWorks 3 It is not necessary to download any configuration files to support the required applications The ProtoNode is pre loaded with tested Profiles Configurations for the supported devices Figure 1 1 ProtoNode Connections to Devices 1 BACnet is a registered trademark of ASHRAE 2 Metasys is a registered trademark of Johnson Contr...

Page 8: ...led indirect systems Built in translation for BACnet IP BACnet MS TP LonWorks Metasys N2 and Modbus TCP Protocols Supports individual units and systems including AERCO s WHM and BST Select protocol and baud rate in the field using simple DIP switch selection Captures alarm and trend history for faster troubleshooting Non volatile memory retains point mappings and programs in the event of power los...

Page 9: ...d WHM Modbus masters The AERCO SSD device is unique because it enables two Modbus masters to bi directionally communicate over RS 485 The AERCO SSD device is also specifically designed to support the BST WHM Automatic failover Feature While the BST WHM role can be transferred to another unit with a different Modbus address the SSD device operates at a fixed and constant Modbus address The fixed SS...

Page 10: ...ProtoNode FPC N34 FPC N35 User Manual CHAPTER 1 Introduction OMM 0150_B 5 20 2021 Technical Support 800 526 0288 Mon Fri 8 am 5 pm EST Page 10 of 140 This Page Left Intentionally Blank ...

Page 11: ...oNode FPC N35 units have the following 3 ports LonWorks Ethernet RS 485 2 2 Point Count Capacity and Registers per Device The total number of Modbus Registers presented by all of the devices attached to the ProtoNode cannot exceed Part number Total Registers FPC N34 1780 1 500 FPC N35 1779 1 500 Figure 2 2 Supported Point Count Capacity Devices Registers Per Device Unit Address Range AM Managing B...

Page 12: ...Devices attached to the ProtoNode Set Modbus Node ID for each of the devices attached to ProtoNode The Modbus Node ID s need to be uniquely assigned between 1 and 255 o The Modbus Node ID that is assigned for each device needs to be documented The Modbus Node ID s assigned are used for designating the Device Instance for BACnet IP and BACnet MS TP Section 2 5 2 The Metasys N2 and Modbus TCP IP Nod...

Page 13: ...P Units ON Off Off Off Figure 2 5 S Bank DIP Switches NOTE For WHM or BST systems auto discovery cannot be done Be sure that the S Bank DIP Switches are set properly 2 4 2 Enabling Auto Discovery Not used on BST WHM or MFC The S3 DIP switch is used to both enable Auto Discovery of known devices attached to the ProtoNode and to save the recently discovered configuration See the table in Figure belo...

Page 14: ...n your PC 5 Enter the IP Address of the ProtoNode the default address is 192 168 1 24 The Configuration Parameters page appears 6 Go to the bottom of the page and find the Active Profiles section This is where you can add equipment profiles Be sure the desired field protocol is already selected as in Step 2 if the field protocol is changed after the equipment profiles are selected they become inva...

Page 15: ...board is OFF A MAC address greater than 127 will cause the ERR LED to light and will disable the ProtoNode from being discovered by the BAS Either set the MAC address to 127 or lower or change the MAX MAC on the Configuration page 2 5 2 BACnet MS TP and BACnet IP FPC N34 Setting the Device Instance Except when Single Node option is selected the BACnet Device Instances will be calculated by adding ...

Page 16: ...the devices attached to the ProtoNode in Section 2 3 2 will be the Metasy N2 or Modbus TCP IP Node_ID s to the field protocols Metasys N2 and Modbus TCP IP Node ID Addressing Metasys N2 and Modbus TCP IP Node ID s range from 1 255 2 5 4 BACnet MS TP or Modbus RTU FPC N34 Setting the Baud Rate for BAS Network B bank DIP switches B0 B3 can be used to set the Field baud rate of the ProtoNode to match...

Page 17: ...nd FPC N35 Showing Connection Ports Figure 3 1b ProtoNode FPC N34 P N 64168 Run Sys Config Error Node Offline Heart Beat SPL RUN ERR RX TX PWR LEDs LEDs A bank B bank S bank RS 485 Bias Jumper RS 485 RX TX Field LED Field Port for B A S Bias Resistor Switch End of Line Termination Switch PWR LED Ethernet Port Jump DO NOT MOVE Device Port for AERCO Equipment RS 485 Termination Jumper Power 9 30 VDC...

Page 18: ...e FPC N34 FPC N35 User Manual CHAPTER 3 Interfacing ProtoNode to Devices OMM 0150_B 5 20 2021 Technical Support 800 526 0288 Mon Fri 8 am 5 pm EST Page 18 of 140 Figure 3 1b LonWorks ProtoNode FPC N35 P N 64169 ...

Page 19: ...he 6 pin Phoenix connector is the same for ProtoNode FPC N34 and FPC N35 Pins 1 through 3 are for Modbus RS 485 devices o The RS 485 GND Pin 3 is not typically connected Pins 4 through 6 are for power Do not connect power wait until Section 3 6 Figure 3 2 Power and RS 485 Connections Device Pins ProtoNode Pin Pin Assignment Pin RS 485 Pin 1 RS 485 Pin RS 485 Pin 2 RS 485 Pin GND Pin 3 RS 485 GND P...

Page 20: ...default positions from the factory for the Biasing jumpers are OFF The OFF position is when the 2 RED biasing jumpers straddle the 4 pins closest to the outside of the board of the ProtoNode see Figure 3 Only turn biasing ON o IF the BAS cannot see more than one device connected to the ProtoNode o AND you have checked all the settings Modbus COM settings wiring and DIP switches o If using a RS232 ...

Page 21: ...ting for this Blue EOL jumper is OFF with the jumper straddling the pins closest to the inside of the board of the ProtoNode o On short cabling runs the EOL jumper may not need to be turned ON If the ProtoNode is placed at one of the ends of the trunk set the blue EOL jumper to the ON position straddling the pins closest to the outside of the board of the ProtoNode Always leave the single Red Jump...

Page 22: ...e Figure 3 6 for the orientation of switch positions referenced below o The default setting from the factory is OFF switch position right side o To enable the EOL Termination turn the EOL switch ON switch position left side Figure 3 5 Connection from ProtoNode to RS 485 Field Network Figure 3 6 RS 485 BMS Network EOL Switch If more than one RS 485 device is connected to the network then the field ...

Page 23: ...nside the wiring area of the ACS BMS II If the AERCO RS232 to RS485 Converter part no 124943 is used the RS 232 side of the converter contains a connector that plugs directly into header connector JP12 BMS or JP5 BMS II ACS If a third party converter is used connect the RS 232 Receive RxD and Transmit TxD wire leads to the internal RS 232 connector JP12 or JP5 as shown in Figures 2 5 and 2 6 DO NO...

Page 24: ...ng ProtoNode to Devices OMM 0150_B 5 20 2021 Technical Support 800 526 0288 Mon Fri 8 am 5 pm EST Page 24 of 140 Figure 3 8 RS 232 Connection to BMS Figure 3 9 RS 232 Connection to ACS BMS II 3 5 1 Modulex BCM Connections Figure 3 10 RS 485 Connection to BCM ...

Page 25: ...Fri 8 am 5 pm EST Page 25 of 140 3 5 2 ECS SP Connections Figure 3 11 RS 485 Connection to ECS SP 3 5 3 C MORE Connections Figure 3 12 RS 485 Connection to C MORE RS 485 Connect ECS SP terminals HE and HF to XPC Port 1a as follows Connect the HF terminal to the ProtoNode s RS485 port Connect the HE terminal to the ProtoNode s RS485 port ...

Page 26: ...s OMM 0150_B 5 20 2021 Technical Support 800 526 0288 Mon Fri 8 am 5 pm EST Page 26 of 140 3 5 4 AM Series Connections Figure 3 13 RS 485 Connection to AM Series RS 485 NOTE For connection of the ProtoNode along with the AERCO AM Series Cascade Sequencer Controller see Appendix I ...

Page 27: ...ing ProtoNode to Devices OMM 0150_B 5 20 2021 Technical Support 800 526 0288 Mon Fri 8 am 5 pm EST Page 27 of 140 3 6 MFC 3000 4000 5000 6000 Connections Figure 3 14 RS 485 Connection to MFC 3000 4000 5000 6000 Figure 3 15 RS 232 Connection to MFC 8000 10000 ...

Page 28: ...ame GND should be connected Power Requirement for ProtoNode External Gateway Current Draw Type ProtoNode Family 12VDC VAC 24VDC VAC 30VDC FPC N34 Typical 170mA 100mA 80mA FPC N34 Maximum 240mA 140mA 100mA FPC N35 Typical 210mA 130mA 90mA FPC N35 Maximum 250mA 170mA 110mA NOTE These values are nominal and a safety margin should be added to the power supply of the host system A safety margin of 25 i...

Page 29: ...Auto Discovery when the unit is powered When power is applied to a ProtoNode that is set to Enable Auto Discovery it will take 10 minutes to complete the discovery of all of the RS 485 devices attached to the ProtoNode Once the ProtoNode has discovered all of the RS 485 devices set the S3 DIP switch to the OFF position to save the current configuration ProtoNode FPC N34 and FPC N35 S3 DIP Switch A...

Page 30: ...rotoNode FPC N34 FPC N35 User Manual CHAPTER 3 Interfacing ProtoNode to Devices OMM 0150_B 5 20 2021 Technical Support 800 526 0288 Mon Fri 8 am 5 pm EST Page 30 of 140 This page intentionally left blank ...

Page 31: ...e are on different IP Networks assign a static IP Address to the PC on the 192 168 1 xxx network For Windows XP 1 Click choose Control Panel and then choose Network Connections 2 Right click on Local Area Connection and choose Properties 3 Highlight For Windows 7 1 Click and choose Control Panel 2 If the Control Panel is displayed by category click Network and Internet and then choose Network and ...

Page 32: ...en a web browser on your PC and enter the IP Address of the ProtoNode the default address is 192 168 1 24 The Web Configurator will be displayed as your landing page see Figure 4 1 Below the Active Profiles heading you should see profiles listed for connected devices If no profiles are present then the wiring baud rate and DIP switch settings must be checked because there is a problem with device ...

Page 33: ... Figure 4 2 Modify the IP Address N1 IP Address field of the ProtoNode Ethernet port If necessary change the Netmask N1 Netmask field Type in a new Subnet Mask If necessary change the IP Gateway Default Gateway field Type in a new IP Gateway NOTE If the ProtoNode is connected to a router the IP Gateway of the ProtoNode should be set to the IP Address of the router that it is connected to Reset Pro...

Page 34: ...ProtoNode FPC N34 FPC N35 User Manual CHAPTER 4 BACnet IP or Modbus TCP IP OMM 0150_B 5 20 2021 Technical Support 800 526 0288 Mon Fri 8 am 5 pm EST Page 34 of 140 This page intentionally left blank ...

Page 35: ...ned IP Address can be discovered using the FS Toolbox utility See Section 5 4 for instructions 5 1 Login to the FieldServer The first time the FieldServer GUI is opened in a browser the IP Address for the gateway will appear as untrusted This will cause the following pop up windows to appear When the Web Server Security Unconfigured window appears read the text and choose whether to move forward w...

Page 36: ...d to 10 40 50 94 unsafe Figure 5 3 Warning Expanded Text When the login screen appears put in the Username default is admin and the Password found on the label of the FieldServer NOTE There is also a QR code in the top right corner of the FieldServer label that shows the default unique password when scanned Figure 5 4 Warning Expanded Text NOTES A user has 5 attempts to login then there will be a ...

Page 37: ...ies are used for authentication To change the web server security mode after initial setup go to Section 5 6 The sections that follow include instructions for assigning the different security modes 5 2 1 HTTPS with Own Trusted TLS Certificate This is the recommended selection and the most secure Please contact your IT department to find out if you can obtain a TLS certificate from your company bef...

Page 38: ...Private Key text into their respective fields If the Private Key is encrypted type in the associated Passphrase 2 Click Save 3 A Redirecting message will appear After a short time the Web Configurator page will open 5 3 HTTPS with Default Untrusted Self Signed TLS Certificate or HTTP with Built in Payload Encryption Simply select one of these options and click the Save button A Redirecting message...

Page 39: ...ver Now on the splash page Check for the IP Address of the desired gateway Figure 5 8 FieldServer Toolbox 5 5 Change User Management Settings From the FS GUI page click Setup in the Navigation panel Click User Management in the navigation panel NOTES If the passwords are lost the unit can be reset to factory settings to reinstate the default unique password on the label For ProtoNode ProtoCessor o...

Page 40: ...ProtoNode FPC N34 FPC N35 User Manual CHAPTER 5 Setup Web Server Security OMM 0150_B 5 20 2021 Technical Support 800 526 0288 Mon Fri 8 am 5 pm EST Page 40 of 140 This page intentionally left blank ...

Page 41: ...sented displaying the current value default 50 000 Change the value of Node_Offset to establish the desired Device Instance values and click the Submit button o Given that Node_Offset Modbus Node_ID Device Instance o Then Node_Offset required Device Instance desired Modbus Node_ID For example o Device 1 has a Modbus Node ID of 1 o Device 2 has a Modbus Node ID of 2 o Device 3 has a Modbus Node ID ...

Page 42: ...ProtoNode FPC N34 FPC N35 User Manual CHAPTER 6 BACnet MS TP and BACnet IP OMM 0150_B 5 20 2021 Technical Support 800 526 0288 Mon Fri 8 am 5 pm EST Page 42 of 140 Figure 6 1 Web Configurator screen ...

Page 43: ...P Address of the ProtoNode has been changed by previous configuration you will need to get the assigned IP Address from the network administrator The Web Configurator will be displayed as your landing page At the bottom left of the page click the Clear Profiles and Restart button Click the System Restart button Once restart is complete all the past profiles that were discovered and or added via th...

Page 44: ...PC N34 FPC N35 User Manual CHAPTER 7 How to Start The Installation Over Clearing Profiles OMM 0150_B 5 20 2021 Technical Support 800 526 0288 Mon Fri 8 am 5 pm EST Page 44 of 140 This page intentionally left blank ...

Page 45: ...hich is different for each LonWorks Network Management Tool If an XIF file is required see steps in Section 8 1 1 to generate XIF Figure 8 1 LonWorks Service Pin Location 8 1 1 Instructions for Downloading XIF File from ProtoNode FPC N35 Using Browser Connect a CAT5 Ethernet cable Straight through or Cross Over between the PC and ProtoNode The Default IP Address of ProtoNode is 192 168 1 24 Subnet...

Page 46: ...the left pane 4 Right click on Local Area Connection and choose Properties 5 Highlight Internet Protocol Version 4 TCP IPv4 and click the Properties button For both Windows XP and Windows 7 click on the Use the following IP address radio button and type in the IP Address Click the OK button twice to complete the process Open a web browser and go to the following address IP Address of ProtoNode fse...

Page 47: ...34 FPC N35 User Manual CHAPTER 8 LonWorks FPC N35 Commissioning ProtoNode OMM 0150_B 5 20 2021 Technical Support 800 526 0288 Mon Fri 8 am 5 pm EST Page 47 of 140 Figure 8 2 Sample of Fserver XIF File Being Generated ...

Page 48: ...Node FPC N34 FPC N35 User Manual CHAPTER 8 LonWorks FPC N35 Commissioning ProtoNode OMM 0150_B 5 20 2021 Technical Support 800 526 0288 Mon Fri 8 am 5 pm EST Page 48 of 140 This page intentionally left blank ...

Page 49: ...ns of ProtoNode in the field without having to have the BAS Integrator on site A Serial or USB to RS 485 converter is needed to test BACnet MS TP 9 1 Downloading the CAS Explorer and Requesting an Activation Key To request the complementary BACnet CAS key Go to http app chipkin com activation twoweek and fill in all the information Enter Vendor Code AERCO2BACnet Once completed the email address th...

Page 50: ... Activation Key 9 2 CAS BACnet Setup These are the instructions to set CAS Explorer up for the first time on BACnet MS TP and BACnet IP 9 2 1 CAS BACnet MS TP Setup Using the Serial or USB to RS 485 converter connect it to your PC and the 3 Pin BACnet MS TP connector on ProtoNode FPC N34 In CAS Explorer do the following o Click on settings o Check the BACnet MS TP box and uncheck the BACnet IP and...

Page 51: ...running the CAS Explorer Connect a straight through or cross Ethernet cable from the PC to ProtoNode In CAS Explorer do the following o Click on settings o Check the BACnet IP box and uncheck the BACnet MS TP and BACnet Ethernet boxes o In the Select a Network Device box select the network card of the PC by clicking on it o Click Ok o On the bottom right hand corner make sure that the BACnet IP bo...

Page 52: ...ProtoNode FPC N34 FPC N35 User Manual CHAPTER 9 CAS BACNET EXPLORER OMM 0150_B 5 20 2021 Technical Support 800 526 0288 Mon Fri 8 am 5 pm EST Page 52 of 140 This Page Left Intentionally Blank ...

Page 53: ...Off Off 37 ON Off ON Off Off ON Off Off 38 Off ON ON Off Off ON Off Off 39 ON ON ON Off Off ON Off Off 40 Off Off Off ON Off ON Off Off 41 ON Off Off ON Off ON Off Off 42 Off ON Off ON Off ON Off Off 43 ON ON Off ON Off ON Off Off Address A0 A1 A2 A3 A4 A5 A6 A7 44 Off Off ON ON Off ON Off Off 45 ON Off ON ON Off ON Off Off 46 Off ON ON ON Off ON Off Off 47 ON ON ON ON Off ON Off Off 48 Off Off Of...

Page 54: ... Off ON 131 ON ON Off Off Off Off Off ON 132 Off Off ON Off Off Off Off ON 133 ON Off ON Off Off Off Off ON 134 Off ON ON Off Off Off Off ON 135 ON ON ON Off Off Off Off ON Address A0 A1 A2 A3 A4 A5 A6 A7 136 Off Off Off ON Off Off Off ON 137 ON Off Off ON Off Off Off ON 138 Off ON Off ON Off Off Off ON 139 ON ON Off ON Off Off Off ON 140 Off Off ON ON Off Off Off ON 141 ON Off ON ON Off Off Off O...

Page 55: ... 214 Off ON ON Off ON Off ON ON 215 ON ON ON Off ON Off ON ON 216 Off Off Off ON ON Off ON ON 217 ON Off Off ON ON Off ON ON 218 Off ON Off ON ON Off ON ON 219 ON ON Off ON ON Off ON ON 220 Off Off ON ON ON Off ON ON 221 ON Off ON ON ON Off ON ON Address A0 A1 A2 A3 A4 A5 A6 A7 222 Off ON ON ON ON Off ON ON 223 ON ON ON ON ON Off ON ON 224 Off Off Off Off Off ON ON ON 225 ON Off Off Off Off ON ON ...

Page 56: ...ProtoNode FPC N34 FPC N35 User Manual APPENDIX A A BANK DIP SWITCH SETTINGS OMM 0150_B 5 20 2021 Technical Support 800 526 0288 Mon Fri 8 am 5 pm EST Page 56 of 140 This Page Left Intentionally Blank ...

Page 57: ...0018 Fire Rate In Input 0x0011 17 0 to 100 Outlet Temp 30003 Outlet Temp Input 0x0002 2 deg F 30 to 245 Display Code 30001 Default Message Display Code Input 0x0000 0 Enum 1 to 102 See Appendix F Unit Status 30002 Unit Status Input 0x0001 1 Enum 0 to 5 0 Disabled 1 Standby 2 Manual Operation 3 Remote Operation 4 Auto Operation Constant Setpoint 5 Fault Run Cycles 30012 30013 Run Cycles Input 0x000...

Page 58: ...On Line 120 On Line But Not Fired Boiler 2 Status 30019 Boiler 2 Status PWM Boiler 2 Input 0x0012 18 Same As Above Boiler 3 Status 30020 Boiler 3 Status PWM Boiler 3 Input 0x0013 19 Same As Above Boiler 4 Status 30021 Boiler 4 Status PWM Boiler 4 Input 0x0014 20 Same As Above Boiler 5 Status 30022 Boiler 5 Status PWM Boiler 5 Input 0x0015 21 Same As Above Boiler 6 Status 30023 Boiler 6 Status PWM ...

Page 59: ...Input 0x0030 42 Same As Above Net Blr 19 Status 30044 Net Boiler 19 Input 0x0031 43 Same As Above Net Blr 20 Status 30045 Net Boiler 20 Input 0x0032 44 Same As Above Net Blr 21 Status 30046 Net Boiler 21 Input 0x0033 45 Same As Above Net Blr 22 Status 30047 Net Boiler 22 Input 0x0034 46 Same As Above Net Blr 23 Status 30048 Net Boiler 23 Input 0x0035 47 Same As Above Net Blr 24 Status 30049 Net Bo...

Page 60: ...Good PV 1 Sensor Broken Bit 6 Loop Break 0 Good closed loop 1 Open Loop Bit 7 Heater Fail 0 No Fault 1 Load fault detected Flow Rate Mixed Temp 30291 Li2 Flow Input 0x0122 290 GPM or F 40 to 205 Standalone SmartPlate EV Points Point Name BACnet Address Lon Name Lon SNVT Modbus Reg Type Modbus Data Address Unit Range SmartPlate EV DHW Out AV 1 nvoSPEVDhwOut_XXX SNVT_count_inc Input 1 F 40 to 220 Se...

Page 61: ...t Drive 40002 Direct Drive Requested Modulation Level Holding 0x0001 1 0 to 100 Mod Lev In Modulation Level In 41201 Monitor Only Global Modulation Level from Cascade Manager Holding 0x04B0 1200 0 to 100 Flow Sens Temp Flow Sensor Temperature 41003 Flow Sensor Temperature Holding 0x03EA 1002 F 14 to 212 Value x 10 Display Code 30001 Status Error Code C more compatible Input 0x0000 0 Enum 2 8 10 18...

Page 62: ...Some Modbus addresses specified in this manual are written generically in hexadecimal decimal format However many Building Automation Systems utilize another form of addressing where 40001 is added to the generic address for a Holding Register address 30001 is added to the generic address for an Input Register address Check the addressing scheme being used by the BAS interfaced to the ProtoNode ...

Page 63: ...o 16 Edge Read Master Address 30109 SMD_BAS_IP_OpVal_ 9 Input 108 0 17 250 Header Temp 30110 SMD_BAS_IP_OpVal_ 10 Input 109 F 30 to 245 Outdoor Temp 30111 SMD_BAS_IP_OpVal_ 11 Input 110 F 70 to 130 Percent Output 30112 SMD_BAS_IP_OpVal_ 12 Input 111 0 to 100 Number of Units Firing 30113 SMD_BAS_IP_OpVal_ 13 Input 112 0 to 8 Cmore 0 to 16 Edge Master Active Setpoint 30114 SMD_BAS_IP_OpVal_ 14 Input...

Page 64: ..._HTR_ xx 2 _ 11 Input xx10 Enum List 0 to 10 see note Unit Size 3xx12 SMD_BAS_IP_HTR_ xx 2 _ 12 Input xx11 Enum List 0 to 21 see note Valve State 3xx13 SMD_BAS_IP_HTR_ xx 2 _ 13 Input xx12 0 Closed 1 Open Net Remote Setpoint 3xx14 SMD_BAS_IP_HTR_ xx 2 _ 14 Input xx13 F 40 to 200 Run Cycles Upper 16 bits 3xx15 SMD_BAS_IP_HTR_ xx 2 _ 15 Input xx14 0 to 65535 see note Run Cycles Lower 16 bits 3xx16 S...

Page 65: ...to 100 SP Setpoint AV xx02 nvoSPHTR_yy_3 SNVT_count_inc Input 3xx02 F 30 to 245 SP Error AV xx03 nvoSPHTR_yy_4 SNVT_count_inc Input 3xx03 Error 0 20 SP Delta Pres AV xx04 nvoSPHTR_yy_5 SNVT_count_inc Input 3xx04 PSI 0 to 100 SP DHW Inlet AV xx05 nvoSPHTR_yy_6 SNVT_count_inc Input 3xx05 F 70 to 245 SP Flow AV xx06 nvoSPHTR_yy_7 SNVT_count_inc Input 3xx06 GPM 0 to 200 SP Boiler Inlet AV xx07 nvoSPHT...

Page 66: ...Rockland Unit Sizes C More Units Edge Units 1 600 MBH 1 Spare 2 800 MBH 2 600 MBH Water Heaters 3 1060 MBH 3 800 MBH Water Heaters 4 1350 MBH 4 1060 MBH Water Heaters 5 600 MBH 5 1350 MBH Water Heaters 6 800 MBH 6 2000 MBH Water Heaters 7 1060 MBH 0 Spare Boilers 8 1350 MBH 1 600 MBH Boilers 9 500 MBH 2 800 MBH Boilers 10 750 MBH 3 1060 MBH Boilers 11 1000 MBH 4 1350 MBH Boilers 12 1 5 MBTU 5 500 ...

Page 67: ...Bit0 C F Bit1 bar psi 101 0065 X Device type 1 Managing Stand alone Boiler 102 0066 X State See state table 103 0067 X Status See status table 104 0068 X Error Code See error list 105 0069 X Warning Code See warning list 106 006A X X Boiler CH setpoint V Depending on units C F 107 006B X X Boiler DHW setpoint V Depending on units C F 108 006C X X Boiler operation 0 x 109 006D X X DHW type 0 x 110 ...

Page 68: ...s 0 65536 hours 130 0082 X Burner Med hours DHW Hours 0 65536 hours 131 0083 X Burner Low hours 0 65536 hours Reserved 150 0096 X Dependent State See state table 151 0097 X Dependent Status See status table 152 0096 X Dependent Error Number See error list 153 0096 X Dependent Firing Rate V 0 100 Reserved 199 00C7 Reserved Appendix B 5 Table 2 AM Controller Managing Parameters Holding Register Acce...

Page 69: ...eserved Appendix B 5 Table 3 AM Dependent Boiler Parameters Holding Register Access Parameter Name Automatic Conversion Range R W 99 0063 X X Control Register Bit 0 Write Enable Bit 14 Controller Reset 100 0064 X X Modbus Units Bit0 C F Bit1 bar psi 101 0065 X Device type 2 Dependent Boiler 102 0066 X State See state table 103 0067 X Status See status table 104 0068 X Error Code See error list 105...

Page 70: ...OK 0 65536 resolution 16 127 007F X Ignition count Failed 0 65536 resolution 1 128 0080 X Flame count Failed 0 65536 resolution 1 129 0081 X Burner High hours CH hours 0 65536 hours 130 0082 X Burner Med hours DHW hours 0 65536 hours 131 0083 X Burner Low hours 0 65536 hours 199 00C7 reserved NOTES 1 Writing to a write able point of an AM Series boiler or heater is a two step process First the Con...

Page 71: ... Address Modbus Units AV 1 AO 1 nvi nvoModUnits_XXX SNVT_count_f 40101 Device Type AI 2 AI 2 nvoDevType_XXX SNVT_count_f 40102 State AI 3 AI 3 nvoState_XXX SNVT_count_f 40103 Status AI 4 AI 4 nvoStatus_XXX SNVT_count_f 40104 Error Code AI 5 AI 5 nvoErrCode_XXX SNVT_count_f 40105 Warning Code AI 6 AI 6 nvoWarnCode_XXX SNVT_count_f 40106 Boiler CH SP AV 7 AO 7 nvi nvoBlrCHSP_XXX SNVT_count_f 40107 B...

Page 72: ... Flame Count Failed AI 29 AI 29 nvoFlmCntFl_XXX SNVT_count_f 40129 Burner High Hours CH Hours AI 30 AI 30 nvoBrnHiHrs_XXX SNVT_time_hour 40130 Burner Med Hours DHW Hours AI 31 AI 31 nvoBrnMedHrs_XXX SNVT_time_hour 40131 Burner Low Hours AI 32 AI 32 nvoBrnLoHrs_XXX SNVT_time_hour 40132 1st Lockout in History AI 33 AI 33 nvo1LkotHst_XXX SNVT_count_f 40133 Time after 1st Lockout AI 34 AI 34 nvoTime1L...

Page 73: ...m_XXX SNVT_count_f 40158 Dependent_2 Firing Rate AI 56 AI 56 nvoD2FirRat_XXX SNVT_lev_percent 40159 Dependent_3 State AI 57 AI 57 nvoD3State_XXX SNVT_count_f 40161 Dependent_3 Satus AI 58 AI 58 nvoD3Satus_XXX SNVT_count_f 40162 Dependent_3 Error Number AI 59 AI 59 nvoD3ErrNum_XXX SNVT_count_f 40163 Dependent_3 Firing Rate AI 60 AI 60 nvoD3FirRat_XXX SNVT_lev_percent 40164 Dependent_4 State AI 61 A...

Page 74: ...od_XXX SNVT_count_f 40204 Controller CH SP AV 81 AO 81 nvi nvoCtlCHSP_XXX SNVT_count_f 40205 Controller DHW SP AV 82 AO 82 nvi nvoCtlDHWSP_XXX SNVT_count_f 40206 High Outdoor Air Temp AV 83 AO 83 nvi nvoHiOATmp_XXX SNVT_count_f 40207 Minimum Outdoor Air SP AV 84 AO 84 nvi nvoMinOASP_XXX SNVT_count_f 40208 Low Outdoor Air Temp AV 85 AO 85 nvi nvoLoOATmp_XXX SNVT_count_f 40209 Maximum Outdoor Air SP...

Page 75: ...40107 Boiler DHW SP AV 8 AO 8 nvi nvoBlrDHWSP_XX X SNVT_count_f 40108 Boiler Operation AV 9 AO 9 nvi nvoBlrOp_XXX SNVT_count_f 40109 DHW Type AV 10 AO 10 nvi nvoDHWType_XXX SNVT_count_f 40110 CH Mode AV 11 AO 11 nvi nvoCHMode_XXX SNVT_count_f 40111 DHW Mode AV 12 AO 12 nvi nvoDHWMode_XXX SNVT_count_f 40112 Supply Temp AI 13 AI 13 nvoSupTmp_XXX SNVT_count_f 40113 Return Temp AI 14 AI 14 nvoRetTmp_X...

Page 76: ...40133 Time after 1st Lockout AI 34 AI 34 nvoTime1Lkot_XXX SNVT_time_hour 40134 2nd Lockout AI 35 AI 35 nvo2LkotHst_XXX SNVT_count_f 40135 Time after 2nd Lockout AI 36 AI 36 nvoTime2Lkot_XXX SNVT_time_hour 40136 3rd Lockout AI 37 AI 37 nvo3LkotHst_XXX SNVT_count_f 40137 Time after 3rd Lockout AI 38 AI 38 nvoTime3kot_XXX SNVT_time_hour 40138 4th Lockout AI 39 AI 39 nvo4Lkot_XXX SNVT_count_f 40139 Ti...

Page 77: ...Tmp_XXX SNVT_count_inc 30003 Display Code dispcode_XXX AV 7 ADF 7 nvoDispCode_XXX SNVT_count_inc 30001 Unit Status unitstat_XXX AV 8 ADF 8 nvoUnitStat_XXX SNVT_count_inc 30002 Run Cycles runcycles_XXX AV 9 ADF 9 nvoRunCycles_XXX SNVT_count_f 30012 30013 Run Hours runhours_XXX AV 10 ADF 10 nvoRunHours_XXX SNVT_count_f 30014 30015 Oxygen Level o2level_XXX AV 11 ADF 11 nvoO2Lev_XXX SNVT_count_inc 300...

Page 78: ...30002 Return Flow Temp returntemp_XXX AV 10 ADF 10 nvoMlxRetTmp_XXX SNVT_count_inc 41004 Appendix C 5 ECS SP Modbus RTU Mappings to BACnet MS TP BACnet IP Metasys N2 Modbus TCP IP and LonWorks Appendix C 5 ECS SP Modbus RTU Mappings to BACnet MS TP BACnet IP Metasys N2 Modbus TCP IP and LonWorks Name Point Name BACnet Object Type BACnet Object ID N2 Data Type N2 Point Address Lon Name Lon SNVT Mod...

Page 79: ...AV 8 ADF 8 nvoBlrOnline_XXX SNVT_count_inc 30009 Last Boiler Fired blrlast_XXX AV 9 ADF 9 nvoLastFired_XXX SNVT_count_inc 30017 Boiler 1 Status blr1stat_XXX AV 10 ADF 10 nvoBlr1Stat_XXX SNVT_count_inc 30018 Boiler 2 Status blr2stat_XXX AV 11 ADF 11 nvoBlr2Stat_XXX SNVT_count_inc 30019 Boiler 3 Status blr3stat_XXX AV 12 ADF 12 nvoBlr3Stat_XXX SNVT_count_inc 30020 Boiler 4 Status blr4stat_XXX AV 13 ...

Page 80: ...7Stat_XXX SNVT_count_inc 30042 Net Boiler 18 Status netblr18stat_XXX AV 35 ADF 35 nvoNetBlr18Stat_XXX SNVT_count_inc 30043 Net Boiler 19 Status netblr19stat_XXX AV 36 ADF 36 nvoNetBlr19Stat_XXX SNVT_count_inc 30044 Net Boiler 20 Status netblr20stat_XXX AV 37 ADF 37 nvoNetBlr20Stat_XXX SNVT_count_inc 30045 Net Boiler 21 Status netblr21stat_XXX AV 38 ADF 38 nvoNetBlr21Stat_XXX SNVT_count_inc 30046 N...

Page 81: ...nt setpoint temp press AI 12 AI 12 nvoCurSP_Tmp_XXX SNVT_count_inc_f 40012 Actual value temp press AI 13 AI 13 nvoActVal_Tp_XXX SNVT_count_inc_f 40013 Flame signal AI 14 AI 14 nvoFlameSig_XXX SNVT_lev_percent 40014 Current fuel throughput AI 15 AI 15 nvoCurFlThr_XXX SNVT_count_inc_f 40015 Current O2 value AI 16 AI 16 nvoCurO2Val_XXX SNVT_lev_percent 40016 Volume unit of gas AI 17 AI 17 nvoVolGsUni...

Page 82: ...ltistage AV 41 AO 41 nvi nvoPreOutMod_XXX SNVT_count_inc_f 40046 Fuel selection AZL AV 42 AO 42 nvi nvoFlSelAZL_XXX SNVT_count_inc_f 40047 Setpoint W1 AV 43 AO 43 nvi nvoSP_W1_XXX SNVT_count_inc_f 40048 Setpoint W2 AV 44 AO 44 nvi nvoSP_W2_XXX SNVT_count_inc_f 40049 Weekday AV 45 AO 45 nvi nvoWeekday_XXX SNVT_count_inc_f 40050 Date Reg 1 AV 46 AO 46 nvi nvoDate_R1_XXX SNVT_count_inc_f 40051 Date R...

Page 83: ...1 AI 71 nvoAZLASN5_XXX SNVT_count_inc_f 40089 AZL5 ASN Reg 6 AI 72 AI 72 nvoAZLASN6_XXX SNVT_count_inc_f 40090 AZL5 ASN Reg 7 AI 73 AI 73 nvoAZLASN7_XXX SNVT_count_inc_f 40091 AZL5 ASN Reg 8 AI 74 AI 74 nvoAZLASN8_XXX SNVT_count_inc_f 40092 AZL5 parameter set code AI 75 AI 75 nvoAZLPrStCd_XXX SNVT_count_inc_f 40093 AZL5 parameter set version AI 76 AI 76 nvoAZLPrStVr_XXX SNVT_count_inc_f 40094 AZL5...

Page 84: ... 6 AI 103 AI 103 nvoBrnr_ID6_XXX SNVT_count_inc_f 40121 Brnr id Reg 7 AI 104 AI 104 nvoBrnr_ID7_XXX SNVT_count_inc_f 40122 Brnr id Reg 8 AI 105 AI 105 nvoBrnr_ID8_XXX SNVT_count_inc_f 40123 Min output gas AI 106 AI 106 nvoMinOutGas_XXX SNVT_lev_percent 40124 Max output gas AI 107 AI 107 nvoMaxOutGas_XXX SNVT_lev_percent 40125 Min output oil AI 108 AI 108 nvoMinOutOil_XXX SNVT_lev_percent 40126 Max...

Page 85: ...ckout Date Day AI 129 AI 129 nvoCrLkDtDay_XXX SNVT_count_inc_f 40409 Current Lockout Time of day Hours AI 130 AI 130 nvoCrLkTmHrs_XXX SNVT_count_inc_f 40410 Current Lockout Time of day Minutes AI 131 AI 131 nvoCrLkTmMin_XXX SNVT_count_inc_f 40411 Current Lockout Time of day Seconds AI 132 AI 132 nvoCrLkTmSec_XXX SNVT_count_inc_f 40412 Current Lockout Startup counter total AI 133 AI 133 nvoCrLkCtTo...

Page 86: ...STERESIS RHYS1 AV 9 AO 9 nvi nvoRHYS1_XXX SNVT_count_inc_f 41283 REMOTE OFF HYST BOTTOM RHYS2 AV 10 AO 10 nvi nvoRHYS2_XXX SNVT_count_inc_f 41285 REMOTE OFF HYST TOP RHYS3 AV 11 AO 11 nvi nvoRHYS3_XXX SNVT_count_inc_f 41287 REMOTE SETPOINT SPR AV 12 AO 12 nvi nvoSPr_XXX SNVT_count_inc_f 41289 REMOTE BURNER OUTPUT RK1 AV 13 AO 13 nvi nvoRk1_XXX SNVT_count_inc_f 41291 REMOTE K2 OUTPUT RK2 AV 14 AO 1...

Page 87: ...BUS WATCHDOG dtt AV 32 AO 32 nvi nvoDtt_XXX SNVT_count_inc_f 44214 FILTER INPUT 1 dF1 AV 33 AO 33 nvi nvoDf1_XXX SNVT_count_inc_f 44216 FILTER INPUT 2 dF2 AV 34 AO 34 nvi nvoDf2_XXX SNVT_count_inc_f 44218 FILTER INPUT 3 dF3 AV 35 AO 35 nvi nvoDf3_XXX SNVT_count_inc_f 44220 ACTUAL VALUE LIMIT LOW oLLo AI 36 AI 36 nvoOlLo_XXX SNVT_count_inc_f 44222 ACTUAL VALUE LIMIT HIGH oLHi AI 37 AI 37 nvoOlLi_XX...

Page 88: ...XX SNVT_count_inc_f 53355 INPUT 2 SCALE LOW SCL2 AV 57 AO 57 nvi nvoScl2_XXX SNVT_count_inc_f 53363 INPUT 2 SCALE HIGH SCH2 AV 58 AO 58 nvi nvoSch2_XXX SNVT_count_inc_f 53365 OFFSET INPUT 2 OFF2 AV 59 AO 59 nvi nvoOff2_XXX SNVT_count_inc_f 53367 OFFSET INPUT 3 OFF3 AV 60 AO 60 nvi nvoOff3_XXX SNVT_count_inc_f 53371 SETPOINT LIMIT SCALE LOW SPL AV 61 AO 61 nvi nvoSPl_XXX SNVT_count_inc_f 53447 SETP...

Page 89: ...BW Inlet T AV 370 nvoSPEVBWInlet_T_XXX SNVT_count_inc Input 370 DHW Inlet T AV 373 nvoSPEVDhwInlet_T_XXX SNVT_count_inc Input 373 DP AV 379 nvoSPEVDP_XXX SNVT_count_inc Input 379 Alarm 1 Out AV 10249 nvoSPEVAlarm1Out_XXX SNVT_count_f Input 10249 Alarm 2 Out AV 10265 nvoSPEVAlarm2Out_XXX SNVT_count_f Input 10265 Alarm 3 Out AV 10281 nvoSPEVAlarm3Out_XXX SNVT_count_f Input 10281 Alarm 4 Out AV 10297...

Page 90: ...HTR_01_ 7 AV 307 Data Float 53 nvoHTR_01_8 inc count 9 Output non polled 30307 1 Flame Strength SMD_BAS_IP_HTR_01_ 8 AV 308 Data Float 54 nvoHTR_01_9 inc count 9 Output non polled 30308 1 Fire Rate In SMD_BAS_IP_HTR_01_ 9 AV 309 Data Float 55 nvoHTR_01_10 inc count 9 Output non polled 30309 1 Fire Rate Out SMD_BAS_IP_HTR_01_ 10 AV 310 Data Float 56 nvoHTR_01_11 inc count 9 Output non polled 30310 ...

Page 91: ...oHTR_02_9 inc count 9 Output non polled 30408 2 Fire Rate In SMD_BAS_IP_HTR_02_ 9 AV 409 Data Float 75 nvoHTR_02_10 inc count 9 Output non polled 30409 2 Fire Rate Out SMD_BAS_IP_HTR_02_ 10 AV 410 Data Float 76 nvoHTR_02_11 inc count 9 Output non polled 30410 2 Unit Type SMD_BAS_IP_HTR_02_ 11 AV 411 Data Float 77 nvoHTR_02_12 inc count 9 Output non polled 30411 2 Unit Size SMD_BAS_IP_HTR_02_ 12 AV...

Page 92: ...e SMD_BAS_IP_HTR_03_ 11 AV 511 Data Float 97 nvoHTR_03_12 inc count 9 Output non polled 30511 3 Unit Size SMD_BAS_IP_HTR_03_ 12 AV 512 Data Float 98 nvoHTR_03_13 inc count 9 Output non polled 30512 3 Value State SMD_BAS_IP_HTR_03_ 13 AV 513 Data Float 99 nvoHTR_03_14 inc count 9 Output non polled 30513 3 Net Remote Setpt SMD_BAS_IP_HTR_03_ 14 AV 514 Data Float 100 nvoHTR_03_15 inc count 9 Output n...

Page 93: ...Net Remote Setpt SMD_BAS_IP_HTR_04_ 14 AV 614 Data Float 120 nvoHTR_04_15 inc count 9 Output non polled 30614 4 Run Cycles Upper SMD_BAS_IP_HTR_04_ 15 AV 615 Data Float 121 nvoHTR_04_16 inc count 9 Output non polled 30615 4 Run Cycles Lower SMD_BAS_IP_HTR_04_ 16 AV 616 Data Float 122 nvoHTR_04_17 inc count 9 Output non polled 30616 4 Run Hours Upper SMD_BAS_IP_HTR_04_ 17 AV 617 Data Float 123 nvoH...

Page 94: ...on polled 30716 5 Run Hours Upper SMD_BAS_IP_HTR_05_ 17 AV 717 Data Float 143 nvoHTR_05_18 inc count 9 Output non polled 30717 5 Run Hours Lower SMD_BAS_IP_HTR_05_ 18 AV 718 Data Float 144 nvoHTR_05_19 inc count 9 Output non polled 30718 5 Oxygen Level SMD_BAS_IP_HTR_05_ 19 AV 719 Data Float 145 nvoHTR_05_20 inc count 9 Output non polled 30719 Blr Addr 6 6 Comm Address SMD_BAS_IP_HTR_06_ 0 AV 800 ...

Page 95: ...9 Output non polled 30819 Blr Addr 7 7 Comm Address SMD_BAS_IP_HTR_07_ 0 AV 900 Data Float 166 nvoHTR_07_1 inc count 9 Output non polled 30900 7 Unit Status SMD_BAS_IP_HTR_07_ 1 AV 901 Data Float 167 nvoHTR_07_2 inc count 9 Output non polled 30901 7 Fault Code SMD_BAS_IP_HTR_07_ 2 AV 902 Data Float 168 nvoHTR_07_3 inc count 9 Output non polled 30902 7 Outlet Temp SMD_BAS_IP_HTR_07_ 3 AV 903 Data F...

Page 96: ...ut non polled 31002 8 Outlet Temp SMD_BAS_IP_HTR_08_ 3 AV 1003 Data Float 189 nvoHTR_08_4 inc count 9 Output non polled 31003 8 FFWD Temp SMD_BAS_IP_HTR_08_ 4 AV 1004 Data Float 190 nvoHTR_08_5 inc count 9 Output non polled 31004 8 Inlet Temp SMD_BAS_IP_HTR_08_ 5 AV 1005 Data Float 191 nvoHTR_08_6 inc count 9 Output non polled 31005 8 Exhaust Temp SMD_BAS_IP_HTR_08_ 6 AV 1006 Data Float 192 nvoHTR...

Page 97: ...t Temp SMD_BAS_IP_HTR_09_ 3 AV 1103 Data Float 209 nvoHTR_09_4 inc count 9 Output non polled 31103 9 FFWD Temp SMD_BAS_IP_HTR_09_ 4 AV 1104 Data Float 210 nvoHTR_09_5 inc count 9 Output non polled 31104 9 Inlet Temp SMD_BAS_IP_HTR_09_ 5 AV 1105 Data Float 211 nvoHTR_09_6 inc count 9 Output non polled 31105 9 Exhaust Temp SMD_BAS_IP_HTR_09_ 6 AV 1106 Data Float 212 nvoHTR_09_7 inc count 9 Output no...

Page 98: ...ed 31203 10 FFWD Temp SMD_BAS_IP_HTR_10_ 4 AV 1204 Data Float 230 nvoHTR_10_5 inc count 9 Output non polled 31204 10 Inlet Temp SMD_BAS_IP_HTR_10_ 5 AV 1205 Data Float 231 nvoHTR_10_6 inc count 9 Output non polled 31205 10 Exhaust Temp SMD_BAS_IP_HTR_10_ 6 AV 1206 Data Float 232 nvoHTR_10_7 inc count 9 Output non polled 31206 10 Air Temp SMD_BAS_IP_HTR_10_ 7 AV 1207 Data Float 233 nvoHTR_10_8 inc ...

Page 99: ...HTR_11_7 inc count 9 Output non polled 31306 11 Air Temp SMD_BAS_IP_HTR_11_ 7 AV 1307 Data Float 253 nvoHTR_11_8 inc count 9 Output non polled 31307 11 Flame Strength SMD_BAS_IP_HTR_11_ 8 AV 1308 Data Float 254 nvoHTR_11_9 inc count 9 Output non polled 31308 11 Fire Rate In SMD_BAS_IP_HTR_11_ 9 AV 1309 Data Float 255 nvoHTR_11_10 inc count 9 Output non polled 31309 11 Fire Rate Out SMD_BAS_IP_HTR_...

Page 100: ...D_BAS_IP_HTR_12_ 9 AV 1409 Data Float 275 nvoHTR_12_10 inc count 9 Output non polled 31409 12 Fire Rate Out SMD_BAS_IP_HTR_12_ 10 AV 1410 Data Float 276 nvoHTR_12_11 inc count 9 Output non polled 31410 12 Unit Type SMD_BAS_IP_HTR_12_ 11 AV 1411 Data Float 277 nvoHTR_12_12 inc count 9 Output non polled 31411 12 Unit Size SMD_BAS_IP_HTR_12_ 12 AV 1412 Data Float 278 nvoHTR_12_13 inc count 9 Output n...

Page 101: ...e SMD_BAS_IP_HTR_13_ 12 AV 1512 Data Float 298 nvoHTR_13_13 inc count 9 Output non polled 31512 13 Value State SMD_BAS_IP_HTR_13_ 13 AV 1513 Data Float 299 nvoHTR_13_14 inc count 9 Output non polled 31513 13 Net Remote Setpt SMD_BAS_IP_HTR_13_ 14 AV 1514 Data Float 300 nvoHTR_13_15 inc count 9 Output non polled 31514 13 Run Cycles Upper SMD_BAS_IP_HTR_13_ 15 AV 1515 Data Float 301 nvoHTR_13_16 inc...

Page 102: ...4 Run Cycles Upper SMD_BAS_IP_HTR_14_ 15 AV 1615 Data Float 321 nvoHTR_14_16 inc count 9 Output non polled 31615 14 Run Cycles Lower SMD_BAS_IP_HTR_14_ 16 AV 1616 Data Float 322 nvoHTR_14_17 inc count 9 Output non polled 31616 14 Run Hours Upper SMD_BAS_IP_HTR_14_ 17 AV 1617 Data Float 323 nvoHTR_14_18 inc count 9 Output non polled 31617 14 Run Hours Lower SMD_BAS_IP_HTR_14_ 18 AV 1618 Data Float ...

Page 103: ...on polled 31717 15 Run Hours Lower SMD_BAS_IP_HTR_15_ 18 AV 1718 Data Float 344 nvoHTR_15_19 inc count 9 Output non polled 31718 15 Oxygen Level SMD_BAS_IP_HTR_15_ 19 AV 1719 Data Float 345 nvoHTR_15_20 inc count 9 Output non polled 31719 Blr Addr 16 16 Comm Address SMD_BAS_IP_HTR_16_ 0 AV 1800 Data Float 346 nvoHTR_16_1 inc count 9 Output non polled 31800 16 Unit Status SMD_BAS_IP_HTR_16_ 1 AV 18...

Page 104: ...HTR_16_ 18 AV 1818 Data Float 364 nvoHTR_16_19 inc count 9 Output non polled 31818 16 Oxygen Level SMD_BAS_IP_HTR_16_ 19 AV 1819 Data Float 365 nvoHTR_16_20 inc count 9 Output non polled 31819 Master Addr 247 Master Control Values 247 Write Cntrl Val to BST WHM SMD_BAS_IP_Ctrl_ 1 write 1 to send Value to WHM AV 51 Data Float 2 nvoCtrl_2 inc count 9 Input Output 40051 247 BST WHM Timeout SMD_BAS_IP...

Page 105: ...OpVal_ 15 AV 115 Data Float 21 nvoOpVal_16 inc count 9 Output non polled 30115 247 Header High Limit SMD_BAS_IP_OpVal_ 16 AV 116 Data Float 22 nvoOpVal_17 inc count 9 Output non polled 30116 247 Header Low Limit SMD_BAS_IP_OpVal_ 17 AV 117 Data Float 23 nvoOpVal_18 inc count 9 Output non polled 30117 247 Header Temp High Limit SMD_BAS_IP_OpVal_ 18 AV 118 Data Float 24 nvoOpVal_19 inc count 9 Outpu...

Page 106: ..._5 SNVT_count_inc Input 33504 SP DHW Inlet AV 3505 nvoSPHTR_50_6 SNVT_count_inc Input 33505 SP Flow AV 3506 nvoSPHTR_50_7 SNVT_count_inc Input 33506 SP Boiler Inlet AV 3507 nvoSPHTR_50_8 SNVT_count_inc Input 33507 Htr Addr 51 Point Name BACnet Address Lon Name Lon SNVT Modbus Reg Type Modbus Data Address SP Outlet AV 3600 nvoSPHTR_51_1 SNVT_count_inc Input 33600 SP Valve Position AV 3601 nvoSPHTR_...

Page 107: ...nput 33704 SP DHW Inlet AV 3705 nvoSPHTR_52_6 SNVT_count_inc Input 33705 SP Flow AV 3706 nvoSPHTR_52_7 SNVT_count_inc Input 33706 SP Boiler Inlet AV 3707 nvoSPHTR_52_8 SNVT_count_inc Input 33707 Htr Addr 53 Point Name BACnet Address Lon Name Lon SNVT Modbus Reg Type Modbus Data Address SP Outlet AV 3800 nvoSPHTR_53_1 SNVT_count_inc Input 33800 SP Valve Position AV 3801 nvoSPHTR_53_2 SNVT_count_inc...

Page 108: ...nput 33904 SP DHW Inlet AV 3905 nvoSPHTR_54_6 SNVT_count_inc Input 33905 SP Flow AV 3906 nvoSPHTR_54_7 SNVT_count_inc Input 33906 SP Boiler Inlet AV 3907 nvoSPHTR_54_8 SNVT_count_inc Input 33907 Htr Addr 55 Point Name BACnet Address Lon Name Lon SNVT Modbus Reg Type Modbus Data Address SP Outlet AV 4000 nvoSPHTR_55_1 SNVT_count_inc Input 34000 SP Valve Position AV 4001 nvoSPHTR_55_2 SNVT_count_inc...

Page 109: ...c Information Type the IP Address of the ProtoNode into your web browser or use the FieldServer Toolbox to connect to the ProtoNode Click on the Diagnostics and Debugging button see Figure 4 1 Click on View and then on click on Connections see Figure E 1 Figure E 1 Error Messages Screen If there are any errors showing on the Connection page please refer to Appendix E 2 below for the relevant wirin...

Page 110: ...isual observations of LEDs on ProtoNode see Appendix E 5 o Check baud rate parity data bits stop bits o Check Modbus device address o Verify wiring o Verify all the Modbus RTU devices were discovered in Web Configurator Chapter 5 Field COM problems o Visual observations of LEDs on ProtoNode see Appendix E 5 o Visual DIP switch settings using correct baud rate and device instance o Verify IP Addres...

Page 111: ...ently being used or download FieldServer Toolbox zip on the Sierra Monitor Corporation webpage under Customer Care Resource Center Software Downloads http www sierramonitor com customer care resource center filters software downloads Extract the executable file and complete the installation Figure E 2 Ethernet Port Location Disable any wireless Ethernet adapters on the PC Laptop Disable firewall a...

Page 112: ...0_B 5 20 2021 Technical Support 800 526 0288 Mon Fri 8 am 5 pm EST Page 112 of 140 o Select Full Diagnostic o If desired the default capture period can be changed o Click on Start Diagnostic o Wait for Capture period to finish The Diagnostic Test Complete window will appear ...

Page 113: ...ical Support 800 526 0288 Mon Fri 8 am 5 pm EST Page 113 of 140 Step 2 Send Log o Once the Diagnostic test is complete a zip file will be saved on the PC o Choose open to launch explorer and have it point directly at the correct folder Send the Diagnostic zip file to support sierramonitor com ...

Page 114: ... more than one ProtoNode on Subnet For both BACnet MS TP and BACnet IP if more than one ProtoNode is connected to the same subnet they must be assigned unique Network_Number values On the main Configuration Parameters screen update the Network Number with the network_nr field and click the Submit button The default value is 50 Figure E 3 Web Configurator showing setting the network number for BACn...

Page 115: ...ll start flashing 20 seconds after power indicating normal operation ERR The SYS ERR LED will go on solid 15 seconds after power up It will turn off after 5 seconds A steady red light indicates a system error on ProtoNode If this occurs immediately report the related system error shown in the error screen of the GUI interface to Sierra Monitor for evaluation NOTE A possible cause for this LED to g...

Page 116: ...min account has unrestricted access to the ProtoNode The User account can view any ProtoNode information but cannot make any changes or restart the ProtoNode The password must be a minimum of eight characters and is case sensitive If you forgot your password click cancel on the password authentication popup window and e mail the password recovery token to the AERCO support team find the appropriat...

Page 117: ...startup The duration of the purge cycle counts up in seconds 5 IGNITION TRIAL XX sec Displayed during ignition trial of startup sequence The duration of cycle counts up in seconds 6 FLAME PROVEN Displayed after flame has been detected for a period of 2 seconds Initially the flame strength is shown in After 5 seconds has elapsed the time and date are shown in place of flame strength 7 WARMUP XX sec...

Page 118: ... RUN The SSOV switch closed for more than 15 seconds during run 22 FLAME LOSS DURING IGN The Flame signal was not seen during ignition or lost within 5 seconds after ignition 23 FLAME LOSS DURING RUN The Flame signal was lost during run 24 HIGH EXHAUST TEMPERATURE The High Exhaust Temperature Limit Switch is closed 25 LOSS OF POWER A power loss occurred The time and date when power was restored is...

Page 119: ...LET TEMP SENSOR FAULT The temperature measured by the Outlet Sensor is out of range 43 FFWD TEMP SENSOR FAULT The temperature measured by the FFWD Sensor is out of range 44 HIGH WATER TEMPERATURE The temperature measured by the Outlet Sensor exceeded the Temp Hi Limit setting 45 LINE VOLTAGE OUT OF PHASE The High AC voltage is out of phase from the low AC voltage 46 STEPPER MOTOR FAILURE The stepp...

Page 120: ...vel is too high 65 RECIRC PUMP FAILURE Heater recirculation pump has malfunctioned 66 IGNITION MONITOR X SEC Waiting for proof of ignition 67 NO FLOW SAFETY LOCKOUT Flow input not registering when boiler is starting up 68 IGNITION SPARK FAULT No ignition current measured when igniter is energized 69 PRE IGNITION X SEC Waiting for SSOV to prove open 70 CLEANING IGNITER X SEC Ignition transformer is...

Page 121: ...EMP COM FAULT The BST Modbus failed to read the header temperature sensor 81 BST LOCAL HEADER SENSOR FAULT The BST direct connected header temperature sensor is out of range 82 BST NET OUTDOOR SENSOR FAULT The BST Modbus connected outdoor air temperature sensor is out of range 83 BST NET OUTDOOR COM FAULT The BST Modbus device failed to read the outdoor air sensor 84 BST LOCAL OUTDR SENSOR FAULT T...

Page 122: ...otoNode FPC N34 FPC N35 User Manual APPENDIX F C MORE STATUS AND FAULT MESSAGES OMM 0150_B 5 20 2021 Technical Support 800 526 0288 Mon Fri 8 am 5 pm EST Page 122 of 140 This Page Left Intentionally Blank ...

Page 123: ...00 500 520 RegVar Temp F 4 1000 500 289 RegVar Temp C ABS_DEG_1 For RegVar 0 1000 500 230 RegVar Temp F For RegVar 0 1000 500 230 RegVar Temp F For RegVar 0 1000 500 128 RegVar Temp C For RegVar 0 1000 500 128 RegVar Temp C Table G 2 Conversion Equations for Temperature Variables Temp to Variable Counts Register Variable Type Degrees Fahrenheit F Degrees Celsius C DEGREES_1 230 115 1000 20 degF Re...

Page 124: ...ProtoNode FPC N34 FPC N35 User Manual APPENDIX G CONVERSION EQUATIONS OMM 0150_B 5 20 2021 Technical Support 800 526 0288 Mon Fri 8 am 5 pm EST Page 124 of 140 This Page Left Intentionally Blank ...

Page 125: ...he third column and identify the Error Table to reference from the fourth column Table H 1 BCM and BMM Fault Code Conversion Table Observed Code Observed Code Code to Look Up in Table Code 0 N A No Fault Code between 1 and 255 BMM 0 Fault Look up code F 2 Code between 256 and 511 BMM 1 Fault Subtract 256 from reading F 2 Code between 512 and 767 BMM 2 Fault Subtract 512 from reading F 2 Code betwe...

Page 126: ...ck flame rod or combustion MANUAL push reset switch or cycle power 5 Flame loss during run Ignition retry Check combustion and wiring MANUAL push reset switch or cycle power 6 High outlet temperature FlowSensor temperature 203 F All burners turned OFF and Pump ON at maximum speed Check Flow Sensor or system pump AUTOMATIC when FlowSensor 176 F 10 Internal Failure Ignition is inhibited Contact Fact...

Page 127: ...ng or change BMM If failure remains check or change gas valve MANUAL push reset switch or cycle power 22 No air flow at burner after fan started for 30 seconds Ignition retry after 60 second delay and failure remains until we have a successful burner operation If fan is stopped check supply voltage and fan wiring If OK try another fan If still not working change the BMM If fan is not stopped check...

Page 128: ...the combustion chamber Ignition is inhibited Check for water in the exhaust manifold 30 Settings Corrupted Ignition is inhibited Pump runs for 5 min at max speed Re program the settings Contact Factory MANUAL cycle the power or send reset message 32 Line voltage too low 96 VAC Wait for proper line voltage 102 VAC Check input voltage else try another BMM AUTOMATIC 40 Low Water Flow Low water flow s...

Page 129: ... at maximum speed Check Flow Sensor or system pump AUTOMATIC when FlowSensor 176 F 37 Crash Ignition is inhibited Change the BCM MANUAL push reset switch to cycle power 38 Settings Corrupted Ignition is inhibited Pump runs for 5 min at max speed Re program the settings Contact Factory MANUAL push reset switch or cycle power 50 Internal Failure Ignition is inhibited Contact Factory for new BCM MANU...

Page 130: ...Node FPC N34 FPC N35 User Manual APPENDIX H FAULT CODES FOR MODULEX E8 CONTROLLER OMM 0150_B 5 20 2021 Technical Support 800 526 0288 Mon Fri 8 am 5 pm EST Page 130 of 140 This Page Left Intentionally Blank ...

Page 131: ... 14 Contents of e2prom is not up to date 15 X ram error 15 Internal software error 16 E2prom error 16 No communication with E2prom 17 E2prom error safety C 17 Wrong safety parameters in e2prom 18 E2prom error Calibration table 18 Wrong calibration table parameters 19 State error 19 Internal software error 20 Rom error 20 Internal software error 21 Rom error C 21 Internal software error 22 Air sw n...

Page 132: ...ror 59 WATER PRESSURE SENSOR 59 Low water pressure 60 FLUE GAS PRESSURE 60 Flue gas pressure error 61 RETURN TEMP 61 Return temperature is higher than stay burning temperature 62 BLOCKED DRAIN 62 Block drain switch is active 64 WD FREQ ERROR 64 No Frequency signal or no communication with the WD 65 PHASE ERROR 65 Hot neutral reversed 66 NET FREQ ERROR 66 Net freq error detected in the main 67 FAUL...

Page 133: ...and handling 13 0x0D POST_PURGE_1 ending boiler demand handling 14 0x0E PUMP_CH_0 handling ch demand without boiler demand 15 0x0F PUMP_CH_1 Post pumping after ch demand end 16 0x10 PUMP_HW_0 handling hw demand without boiler demand 17 0x11 PUMP_HW_1 Post pumping after dhw demand end 18 0x12 ALARM_1 Error handling 19 0x13 ERROR_CHECK error handling 20 0x14 BURNER_BOOT controller re start 21 0x15 C...

Page 134: ...Technical Support 800 526 0288 Mon Fri 8 am 5 pm EST Page 134 of 140 Appendix I 5 Cascade Connection of AM Boiler with ProtoNode The diagram below shows MODBUS connection for AM Series boilers with serial number up to 14999999 Figure I 1 MODBUS connection to AM Series boilers with serial number 14999999 ...

Page 135: ...S TABLES OMM 0150_B 5 20 2021 Technical Support 800 526 0288 Mon Fri 8 am 5 pm EST Page 135 of 140 The diagram below shows MODBUS connection for AM Series boilers with serial number above 15000000 Figure I 2 MODBUS connection to AM Series boilers with serial number 15000000 ...

Page 136: ...M Series Cascade Sequencer Controller OMM 0101 GF 146 CS and Figure I 2 above 2 Connect a daisy chain between terminals 18 19 and 20 of all units see Figure I 1 or I 2 3 Connect the daisy chain to the Rx Tx terminals of the ProtoNode see Figures I 1 or I 2 4 Using the display of the heater set parameter 3085 on each heater as shown below for instruction on how to change parameter 3085 see the AM S...

Page 137: ...rtified Power Requirements Multi mode power adapter 9 30VDC or 12 24VAC Physical Dimensions 11 5 cm L x 8 3 cm W x 4 1 cm H 4 5 x 3 2 x 1 6 in Weight 0 2 kg 0 4 lbs Operating Temperature 40 C to 75 C 40 F to167 F Surge Suppression EN61000 4 2 ESD EN61000 4 3 EMC EN61000 4 4 EFT Humidity 5 90 RH non condensing Specifications subject to change without notice Figure J 1 Specifications Appendix J 2 Co...

Page 138: ...Page 138 of 140 o Be constructed of materials rated VW 1 or FT 1 or better If the unit is to be installed in an operating environment with a temperature above 65 C it should be installed in a Restricted Access Area requiring a key or a special tool to gain access This device must not be connected to a LAN segment with outdoor wiring ...

Page 139: ...ident improper maintenance installation or application or on which original identification marks have been removed or altered This Limited Warranty also will not apply to interconnecting cables or wires consumables or to any damage resulting from battery leakage In all cases Sierra Monitor Corporation s responsibility and liability under this warranty shall be limited to the cost of the equipment ...

Page 140: ... Fri 8 am 5 pm EST Page 140 of 140 AERCO International Inc 2021 Change Log Date Description Changed By 4 15 2020 Rev A Initial Release 5 20 2021 Rev B Added support for SmartPlate EV Sections 2 4 1 3 5 2 Appendix B2 Appendix B4 Appendix C5 and C8 Appendix D Added new Section 5 Setup Web Server Chris Blair ...

Reviews: