Watt Stopper DSW-301 Installation Instructions Manual Download Page 5

DSW-302 and DSW-302-347 

Dual Circuit Wiring

DSW-301 and DSW-301-347 Wiring

Breakaway 

tab

Optional neutral 
terminals behind 
breakaway tab

6" flying leads for 
line, load, ground 
and multi-way 
connections

Optional Neutral Wiring

For applications requiring neutral wiring, remove 
tab as shown to expose terminals for wiring.

                                                                          

Black

Load

Red

Black

Neutral

Neutral

(optional)

Line    

Neutral

(optional)

Ground

Green
Green

Ground

Green
Green

Yellow

traveler

Yellow

Multi-Way

The Multi-Way capability is available on all models. Sensors can easily be 
wired together for convenient control of a common load. When wiring this 
way, only use 300 series sensors. Multi-Way in 300 series is not compatible 
with prior sensor models.

The following princlples apply for Multi-Way:

• 

All units can see each other’s push button events and respond accord-

ingly.

• 

All units can see each other’s PIR trigger event. The response will be 

determined by the Light Level setting and/or conditions of the space of 

the detecting sensor.

• 

The time delay for all units is defined by the unit with the smallest time 

delay

                        Typical wiring

      (DSW-301 or DSW-301-347 - up to 4 sensors)

Summary of Contents for DSW-301

Page 1: ...1200W ballast E ballast LED 1 6 HP 347VAC 1500W ballast LED 1 6 HP Time Delay Adjustment 5 to 30 minutes Walk Through Mode 3 minutes if no activity after 30 sec Test Mode 10 min with 5 sec time delay...

Page 2: ...where the PIR is detecting movement outside of the desired area also consider masking the lens and where heat sources cause unnecessary activation Low 50 DIP 4 ON Unit will beep at one minute at 30 se...

Page 3: ...setting table in order to deem the area occupied Both requires motion detection by the PIR and the Ultrasonic Either requires motion detection by only one technology PIR requires motion detection by...

Page 4: ...utton for each load and the lights will turn ON There is a delay due to initialpower up of the sensor that only occurs during installation 5 Test and adjust the sensor INSTALLATION DSW 302 and DSW 302...

Page 5: ...on all models Sensors can easily be wired together for convenient control of a common load When wiring this way only use 300 series sensors Multi Way in 300 series is not compatible with prior sensor...

Page 6: ...er delay for the sensor set in Manual ON mode or instant re trigger for the sensor set in Auto ON mode After the re trigger delay elapses the ON OFF button of the sensor set in Manual ON mode must be...

Page 7: ...se wiring Black Black Neutral Neutral optional Line Yellow Red Primary Load Brown Secondary Load Neutral optional Ground Green Green Ground Green Green Red Brown Blue Blue Black Black Neutral Ground G...

Page 8: ...button The DSW 302 contains two relays and two ON OFF buttons to allow control of one or two loads independently Pressing a button toggles the state of the corresponding relay Optional Neutral is als...

Page 9: ...minutes Test 20 min 15 minutes 30 minutes Time Delay 5 6 Trigger Mode Initial Occupancy Maintain Occupancy Re trigger seconds duration Option C Both Both Both 5 Standard Either 5 Either Option A Eithe...

Page 10: ...e button assembly Gently pull it away from the unit When the adjustments are completed replace the button cap by inserting its hinges into the tabs on the main unit and then squeeze the top of the but...

Page 11: ...ion Verify that there is no significant heat source e g high wattage light bulb mounted near the sensor 3 Verify that the trimpot is not pointing at Service red LED ON If so rotate the trimpot to it s...

Page 12: ...s in materials and workmanship for a period of five 5 years There are no obligations or liabilities on the part of WattStopper for consequential damages arising out of or in connection with the use or...