Watt Stopper DSW-301 Installation Instructions Manual Download Page 4

1.  Make sure that the power has been turned OFF at the circuit breaker.
2.  Connect wires to the DSW flying leads as shown in the wiring diagram below 

that is appropriate to the DSW model and electrical supply.

 The ground wire 

(green) must be fastened to ground for 

the sensor to work properly

3.   Attach the DSW to the wall box by inserting 

screws into the two wide holes on the top 

and bottom of the attached metal bracket. 

Match them up with the holes in the wall 

box and tighten.

4.   Turn the circuit breaker 

ON. Wait one minute, 

then push the ON/OFF 

button for each load and 

the lights will turn ON. 

There is a delay due to 

initialpower-up of the 

sensor that only occurs 

during installation. 

5. Test and adjust the sensor 

INSTALLATION

DSW-302 and DSW-302-347 

Bi-Level Wiring

DSW-302 and DSW-302-347 

Dual Circuit Wiring

WARNING

TURN THE POWER OFF AT THE CIRCUIT BREAKER 

BEFORE INSTALLING THE SENSOR OR WORKING ON THE LOAD.

#12 — #14 AWG

Cu Wire Only

Strip Gage

1/2"

12.7mm

Load

Red

Black

Neutral

Line    

Green

Green

Neutral

(optional)

Ground

Yellow

DSW-301 and DSW-301-347 Wiring

Red

Black

Neutral

Line    

Green

Green

Ground

Blue

Primary

Load

Secondary

Load

Neutral

(optional)

Brown

Yellow

Red

Black

Neutral

Line 1    

Green

Green

Ground

Blue

Primary

Load

Brown

Secondary

Load

Line 2    

Neutral

Neutral

(optional)

Yellow

Summary of Contents for DSW-301

Page 1: ...1200W ballast E ballast LED 1 6 HP 347VAC 1500W ballast LED 1 6 HP Time Delay Adjustment 5 to 30 minutes Walk Through Mode 3 minutes if no activity after 30 sec Test Mode 10 min with 5 sec time delay...

Page 2: ...where the PIR is detecting movement outside of the desired area also consider masking the lens and where heat sources cause unnecessary activation Low 50 DIP 4 ON Unit will beep at one minute at 30 se...

Page 3: ...setting table in order to deem the area occupied Both requires motion detection by the PIR and the Ultrasonic Either requires motion detection by only one technology PIR requires motion detection by...

Page 4: ...utton for each load and the lights will turn ON There is a delay due to initialpower up of the sensor that only occurs during installation 5 Test and adjust the sensor INSTALLATION DSW 302 and DSW 302...

Page 5: ...on all models Sensors can easily be wired together for convenient control of a common load When wiring this way only use 300 series sensors Multi Way in 300 series is not compatible with prior sensor...

Page 6: ...er delay for the sensor set in Manual ON mode or instant re trigger for the sensor set in Auto ON mode After the re trigger delay elapses the ON OFF button of the sensor set in Manual ON mode must be...

Page 7: ...se wiring Black Black Neutral Neutral optional Line Yellow Red Primary Load Brown Secondary Load Neutral optional Ground Green Green Ground Green Green Red Brown Blue Blue Black Black Neutral Ground G...

Page 8: ...button The DSW 302 contains two relays and two ON OFF buttons to allow control of one or two loads independently Pressing a button toggles the state of the corresponding relay Optional Neutral is als...

Page 9: ...minutes Test 20 min 15 minutes 30 minutes Time Delay 5 6 Trigger Mode Initial Occupancy Maintain Occupancy Re trigger seconds duration Option C Both Both Both 5 Standard Either 5 Either Option A Eithe...

Page 10: ...e button assembly Gently pull it away from the unit When the adjustments are completed replace the button cap by inserting its hinges into the tabs on the main unit and then squeeze the top of the but...

Page 11: ...ion Verify that there is no significant heat source e g high wattage light bulb mounted near the sensor 3 Verify that the trimpot is not pointing at Service red LED ON If so rotate the trimpot to it s...

Page 12: ...s in materials and workmanship for a period of five 5 years There are no obligations or liabilities on the part of WattStopper for consequential damages arising out of or in connection with the use or...