COVER PLATES
WattStopper DSW series wall switches fit behind industry standard
decorator-style switch cover plates. Cover plates are not included.
Units come in the following colors, which are indicated by the final suffix of
the catalog number (shown here in parentheses):
White (-W), Light Almond (-LA), Ivory (-I), Grey (-G), Black (-B).
Lights do not turn OFF
1. There can be up to a 30 minute time delay after the last motion is
detected. To verify proper operation, set DIP switch 1 to ON, then reset
switches 1 and 2 to OFF to start Test Mode. Move out of view of the
sensor. The lights should turn OFF in approximately 5 seconds.
2. Verify that the sensor is mounted at least six feet (2 meters) away from
any heating/ventilating/air conditioning device that may cause false
detection. Verify that there is no significant heat source (e.g., high
wattage light bulb) mounted near the sensor.
3. Verify that the trimpot is not pointing at “Service” (red LED ON). If so,
rotate the trimpot to it’s middle setting (pointing up). The Service setting
allows users to operate the sensor as a service switch in the unlikely
event of a failure.
4. If the lights still do not turn OFF, call 800.879.8585 for technical support.
Sensing motion outside desired areas
1. Select PIR Sensitivity — Low (DIP switch 4 = ON) if necessary.
2. Mask the PIR sensor’s lens to eliminate unwanted coverage area.
3. Adjust the Ultrasonic Sensitivity. Rotate trimpot counterclockwise to
reduce sensitivity.
If Red LED is blinking all the time and the sensor features don’t
work.
1. Check the Ultrasonic trimpot. If it is set at fully counter-clockwise (MIN)
the unit is in Service Mode. Set the trimpot to a mid-range position.
2. If re-setting the trimpot does not clear the LED call technical support.