Santa Clara, CA 95050
800.879.8585
Installation Instructions
Specifications
Voltages:
DSW-301 & DSW-302. . . . . . . . . . . . . .120/277VAC, 50/60Hz
DSW-301-347 & DSW-302-347 . . . . . . . . ..347VAC, 50/60Hz
Load Limits for relay 1:
@120VAC . .1000W tungsten, ballast, E-ballast, LED, 1/4 HP
@277VAC. . . . . . . . . 1200W ballast, E- ballast, LED, 1/4 HP
@347VAC . . . . . . . . . . . . . . . . . . 1500W ballast, LED, 1/4 HP
Load Limits for relay 2:
@120VAC . . .800W tungsten, ballast, E-ballast, LED, 1/6 HP
@277VAC . . . . . . . . . 1200W ballast, E-ballast, LED, 1/6 HP
@347VAC . . . . . . . . . . . . . . . . . . 1500W ballast, LED, 1/6 HP
Time Delay Adjustment . . . . . . . . . . . . . . . . . . . .5 to 30 minutes
Walk-Through Mode . . . . 3 minutes if no activity after 30 sec.
Test Mode . . . . . . . . . . . . . . . . . 10 min. with 5 sec. time delay
PIR Adjustment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .High or Low
Ultrasonic Adjustment . . . . . . . . . . . Minimum to Maximum, Off
Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40kHz
Light Level Adjustment . . . . . . . . . . . . . . . . . . . . . . 8fc to 180+fc
Alerts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Selectable Audible
Optional Neutral . . . . . . . . . . . . . . . . . . . . . . . . . . . . .All models
Multi-Way Capability . . . . . . . . . . . . . . . . . . . . . . . . ..All models
Terminal screw torque . . . . . . . . . . . . . . . 16 lbf-in (18 kgf-cm)
DSW-301/DSW-301-347
DSW-302/DSW-302-347
Dual Technology Multi-Way Wall Switch
Occupancy Sensors
DSW-301
DSW-302
DSW-301-347
DSW-302-347