Watt Stopper CI-200 Installation Instructions Manual Download Page 6

SENSOR ADJUSTMENT

The sensor comes factory preset and ready for 

operation. If testing of operation is desired: 

•  Remove the sensor’s cover (twist).
•  Refer to the 

DIP switch settings chart

 below 

for switch configurations.

•  Make sure that office furniture and fixtures are 

in place.

1.  Restore power to the lighting circuits 

and turn the lights on.
•  There is a 

one minute warm-up

 

when power is initially restored 

to the sensor before the sensor 

works properly.

2.  For testing, set the 

Time Delay

 to 

minimum (15 secs.).

3.  Set 

Sensitivity

 to maximum. 

4.  Turn 

Light Level

 Adjustment trimpot 

to maximum. 

5.  Replace the sensor’s cover then 

move away from sensor and be still.

The lights should go off after 15 

seconds. If lights remain on, see 

Unwanted Sensor Activations under 

Troubleshooting.
With movement in the area, the 

lights should turn back on.

6.  If using the 

light level

 feature 

(otherwise skip to step 7), turn the 

adjustment trimpot to minimum, and 

repeat step 5. Unless it is very dark, 

when the lights turn off, the lights 

controlled by light level should not 

turn back on even with movement in 

the area. 
Until ready to make the final adjustment, leave the setting at maximum. 

The controlled lights will then not be affected by ambient light levels.

To make the light level adjustment:

 (The final light level setting for 

normal operation should be made at a time when, with the lights off, 

the ambient light level is at the point where it is desired for the lights 

to turn on.) 

Set the Time Delay and the Light Level to minimum, then be still 

until the lights turn off (about 15 seconds). Slowly turn the light level 

adjustment toward maximum until the lights turn on—then turn it back 

slightly. At this setting the lights will not turn on if ambient light levels 

are above the current level.

7.  Set the desired 

Time Delay

 for operation (DIP switches #1 – 6).  

Factory preset Time Delay is 20 minutes; other suggestions are:  

Offices and conference rooms (10 minutes), Classrooms (10 minutes), 

Warehouses (6 minutes), Hallways (4 minutes).

LED

Light Level

Adjustment

DIP Switch Control

for Time Delay and

Sensitivity

MAX

MIN

= ON    

 

   = OFF

= Factory Presets

DIP Switch #

15 seconds

4 minutes

6 minutes

8 minutes

10 minutes

12 minutes

14 minutes

16 minutes

18 minutes

20 minutes

22 minutes

24 minutes

26 minutes

28 minutes

2 minutes

1 2 3 4 5 6

30 minutes

Minimum

Medium Low

Medium High

Maximum

7 8

DIP Switch #

Time delay

Sensitivity

Service

Call 800.879.8585 For Technical Support

Summary of Contents for CI-200

Page 1: ...emperature 32 to 131 F 0 to 55 C Time Delay Adjustment 15 seconds 30 minutes PIR Coverage Model CI 200 up to 1200ft2 Model CI 200 1 up to 500ft2 Light Level Adjustment 1 190FC Sensitivity Adjustment M...

Page 2: ...overage Patterns The CI 200 has a multi cell multi tier Fresnel lens with a field of view of 360 The sensor has two lens pattern options The Extended Range Lens will cover up to 1200 sq ft when mounte...

Page 3: ...more than 12 14ft you may start to significantly reduce sensitivity Often the best location to install a CI 200 in a closed office is off center see fig 1 Avoid placing a sensor directly in line with...

Page 4: ...ation of coverage in unwanted areas The mask is cut as needed and mounted onto anchor pins in the sensor s cover IMPORTANT Do not use the mask if full coverage is desired IMPORTANT Before securing the...

Page 5: ...a second load for occupancy and light level ambient light control connect BLUE wire from power pack to yellow wire on sensor BLUE wire from slave pack to blue wire on sensor BLACK wire from slave pack...

Page 6: ...nal adjustment leave the setting at maximum The controlled lights will then not be affected by ambient light levels To make the light level adjustment The final light level setting for normal operatio...

Page 7: ...problem may be in the sensor Turn Sensitivity and Time Delay to minimum and allow the sensor to time out If the lights turn off the sensor is working correctly See Unwanted Sensor Activations next pag...

Page 8: ...cy Sensor with High Density Reduced Range Lens BZ 50 Power Pack 120 277VAC 50 60Hz 20A ballast or incandescent B347D P Power Pack 347VAC 60Hz 150mA 15A ballast S120 277 347E P Slave Pack 120 277VAC 60...

Reviews: