Watt Stopper CI-200 Installation Instructions Manual Download Page 5

WIRING DIRECTIONS

 

CAUTION

TURN POWER OFF AT CIRCUIT  

BREAKER BEFORE WIRING SENSOR

Watt Stopper B series 

power packs

 supply power for up to 5 CI-200s. 

When using more sensors than this, multiple power packs are required.
For all configurations—connect the low voltage:

•  RED wire (+24VDC) from power pack to VIOLET wire on sensor. 

BLACK wire (Return) from power pack to GREEN wire on sensor.

Connections for the following configurations:  

(Refer to wiring diagram below)

Single lighting load controlled by occupancy only

—connect:

•  BLUE wire from power pack to yellow wire on sensor.

Single lighting load controlled by occupancy, dependent on light level

 

(ambient light)—connect:

•  BLUE wire from power pack to blue wire on sensor.

One lighting load for occupancy control, and a second load  

for occupancy and light level 

(ambient light)

 control

—connect:

•  BLUE wire from power pack to yellow wire on sensor.
•  BLUE wire from 

slave pack

 to blue wire on sensor.

•  BLACK wire from 

slave pack

 to gray wire on sensor.

Isolated Relay

(The Isolated Relay is rated for 1A @24VDC or 24VAC) 

 Connect the wires necessary to the application that requires this output.

•  RED (Common) (must be used for proper operation)
•  BROWN (Normally Closed)—Open when occupancy is detected.
•  ORANGE (Normally Open)—Closed when occupancy is detected.

White (Neutral)

Red (Load)

Red (Line)

White

Black

Hot

N

POWER PACK

Red

Black

Blue

Switch

Lighting

Load

Control Output 24VDC

Common

+24VDC

Light Level Output 24VDC

Normally Closed Contact 
Common 
Normally Open Contact

Isolated Relay Outputs 

Black

Blue

Control Return

 Wires

1-

BRN

2-

RED

3-

ORN

4-

YEL

5-

GRN

6-

BLU

7-

VIO

8-

GRA

Light

Level

Lighting

Load

SLAVE

PACK

Red (load)

Hot

OFF switch

N

CI-200

Check Our Web Site For FAQs: www.wattstopper.com

Summary of Contents for CI-200

Page 1: ...emperature 32 to 131 F 0 to 55 C Time Delay Adjustment 15 seconds 30 minutes PIR Coverage Model CI 200 up to 1200ft2 Model CI 200 1 up to 500ft2 Light Level Adjustment 1 190FC Sensitivity Adjustment M...

Page 2: ...overage Patterns The CI 200 has a multi cell multi tier Fresnel lens with a field of view of 360 The sensor has two lens pattern options The Extended Range Lens will cover up to 1200 sq ft when mounte...

Page 3: ...more than 12 14ft you may start to significantly reduce sensitivity Often the best location to install a CI 200 in a closed office is off center see fig 1 Avoid placing a sensor directly in line with...

Page 4: ...ation of coverage in unwanted areas The mask is cut as needed and mounted onto anchor pins in the sensor s cover IMPORTANT Do not use the mask if full coverage is desired IMPORTANT Before securing the...

Page 5: ...a second load for occupancy and light level ambient light control connect BLUE wire from power pack to yellow wire on sensor BLUE wire from slave pack to blue wire on sensor BLACK wire from slave pack...

Page 6: ...nal adjustment leave the setting at maximum The controlled lights will then not be affected by ambient light levels To make the light level adjustment The final light level setting for normal operatio...

Page 7: ...problem may be in the sensor Turn Sensitivity and Time Delay to minimum and allow the sensor to time out If the lights turn off the sensor is working correctly See Unwanted Sensor Activations next pag...

Page 8: ...cy Sensor with High Density Reduced Range Lens BZ 50 Power Pack 120 277VAC 50 60Hz 20A ballast or incandescent B347D P Power Pack 347VAC 60Hz 150mA 15A ballast S120 277 347E P Slave Pack 120 277VAC 60...

Reviews: