WIRING DIRECTIONS
CAUTION
TURN POWER OFF AT CIRCUIT
BREAKER BEFORE WIRING SENSOR
Watt Stopper B series
power packs
supply power for up to 5 CI-200s.
When using more sensors than this, multiple power packs are required.
For all configurations—connect the low voltage:
• RED wire (+24VDC) from power pack to VIOLET wire on sensor.
BLACK wire (Return) from power pack to GREEN wire on sensor.
Connections for the following configurations:
(Refer to wiring diagram below)
Single lighting load controlled by occupancy only
—connect:
• BLUE wire from power pack to yellow wire on sensor.
Single lighting load controlled by occupancy, dependent on light level
(ambient light)—connect:
• BLUE wire from power pack to blue wire on sensor.
One lighting load for occupancy control, and a second load
for occupancy and light level
(ambient light)
control
—connect:
• BLUE wire from power pack to yellow wire on sensor.
• BLUE wire from
slave pack
to blue wire on sensor.
• BLACK wire from
slave pack
to gray wire on sensor.
Isolated Relay
(The Isolated Relay is rated for 1A @24VDC or 24VAC)
Connect the wires necessary to the application that requires this output.
• RED (Common) (must be used for proper operation)
• BROWN (Normally Closed)—Open when occupancy is detected.
• ORANGE (Normally Open)—Closed when occupancy is detected.
White (Neutral)
Red (Load)
Red (Line)
White
Black
Hot
N
POWER PACK
Red
Black
Blue
Switch
Lighting
Load
Control Output 24VDC
Common
+24VDC
Light Level Output 24VDC
Normally Closed Contact
Common
Normally Open Contact
Isolated Relay Outputs
Black
Blue
Control Return
Wires
1-
BRN
2-
RED
3-
ORN
4-
YEL
5-
GRN
6-
BLU
7-
VIO
8-
GRA
Light
Level
Lighting
Load
SLAVE
PACK
Red (load)
Hot
OFF switch
N
CI-200
Check Our Web Site For FAQs: www.wattstopper.com