Watt Stopper CI-200 Installation Instructions Manual Download Page 3

PLACEMENT

The effective coverage distances may be slightly less than the maximum 

sensing distance (see Coverage Patterns), depending upon obstacles such 

as furniture or partitions, and this must be considered when planning the 

number of sensors and their positioning. See the list below for approximate 

coverage distances for different types of motion. 

Approximate coverage, for a mounting height of 8 feet:

Lens option 

Walking motion 

Workstation (hand motion)

Extended Range  up to 22ft radius (1200 sq ft)   12ft radius  (500 sq ft)
High Density 

up to 12ft radius (500 sq ft)  9ft radius (300 sq ft)

The CI-200 sensor can be mounted at various heights.

 When you will be 

mounting at heights other than 12ft, be 

aware that as you decrease the mounting 

height, you will decrease the range and 

increase the sensitivity to smaller motions. 

Conversely, when you increase the height, 

you will increase the range and decrease 

the sensitivity to smaller motions. At 

heights of more than 12 -14ft, you may 

start to significantly reduce sensitivity.
Often the best location to install a CI-200 in 

closed office

 is off-center (see fig.1). Avoid 

placing a sensor directly in line with an open 

door in which it has a clear view out, as the 

sensor may detect people walking by. 
For 

open office areas

 with partitions it is 

best to place sensors over intersections of 

four workstations (see fig. 2). 
Also avoid placing the sensors close to 

air ducts

, as rapid air currents or the 

differences in temperatures may cause false 

activations. For large areas of coverage use 

multiple sensors.

Sensor

36'

36'

Sensor

12'

18'

fig. 1

fig. 2

A 4-S junction box can be used with a 3” mud-ring when local building codes 

mandate that low voltage connections be contained in a junction box.
Otherwise a 3” mud-ring or the provided ceiling attachment ring can be used.

IMPORTANT: If the lens will be masked

, the junction box or mud ring may 

need to be positioned so that the mask is oriented properly when the sensor 

is installed (see Masking).

INSTALLATION

CAUTION

TURN POWER OFF AT CIRCUIT  

BREAKER BEFORE WIRING SENSOR

Check Our Web Site For FAQs: www.wattstopper.com

Summary of Contents for CI-200

Page 1: ...emperature 32 to 131 F 0 to 55 C Time Delay Adjustment 15 seconds 30 minutes PIR Coverage Model CI 200 up to 1200ft2 Model CI 200 1 up to 500ft2 Light Level Adjustment 1 190FC Sensitivity Adjustment M...

Page 2: ...overage Patterns The CI 200 has a multi cell multi tier Fresnel lens with a field of view of 360 The sensor has two lens pattern options The Extended Range Lens will cover up to 1200 sq ft when mounte...

Page 3: ...more than 12 14ft you may start to significantly reduce sensitivity Often the best location to install a CI 200 in a closed office is off center see fig 1 Avoid placing a sensor directly in line with...

Page 4: ...ation of coverage in unwanted areas The mask is cut as needed and mounted onto anchor pins in the sensor s cover IMPORTANT Do not use the mask if full coverage is desired IMPORTANT Before securing the...

Page 5: ...a second load for occupancy and light level ambient light control connect BLUE wire from power pack to yellow wire on sensor BLUE wire from slave pack to blue wire on sensor BLACK wire from slave pack...

Page 6: ...nal adjustment leave the setting at maximum The controlled lights will then not be affected by ambient light levels To make the light level adjustment The final light level setting for normal operatio...

Page 7: ...problem may be in the sensor Turn Sensitivity and Time Delay to minimum and allow the sensor to time out If the lights turn off the sensor is working correctly See Unwanted Sensor Activations next pag...

Page 8: ...cy Sensor with High Density Reduced Range Lens BZ 50 Power Pack 120 277VAC 50 60Hz 20A ballast or incandescent B347D P Power Pack 347VAC 60Hz 150mA 15A ballast S120 277 347E P Slave Pack 120 277VAC 60...

Reviews: